Installation Instructions
Fig. 13
5.3
Electrical Connection
•
The power cord should be laid in a way preventing anyone from threading on it
or tripping against it.
•
In normal operation or maintenance, the power cord cannot be stretched out nor
crushed.
Fig. 14
•
For the safety of the operator and the appliance, provide for proper grounding
pursuant to the safety regulations in force.
•
The appliance complies with the EN/IEC 61000-3-11 standard, on condition that
the system impedance Z
110644
•
To provide for stability, level the appliance
by screwing the feet in or out.
•
Correct levelling is indispensable in
ensuring optimum performance of the
appliance.
•
A universal main disconnecter must be used
that would disconnect all contacts, including
the zero distributor. The disconnected contact
must feature at least a 3 mm gap. The switch
must be activated by a thermo-magnetic
safety device or be coupled to fuses. The
fuses and the switch must be designed for the
power provided on the rating plate.
•
The main switch must be located in the power
line near the installation place. Only one
appliance may be permanently connected to
the main switch.
•
Verify if the technical specification of the
appliance (see the rating plate) corresponds
to the characteristics of the local electric
mains grid.
is lower or equals Z
sys
at the interface between the
max