Installation manual
4.2.1.4.4 Dual-channel sensor with time monitoring and cross-circuit testing
By using two independent test pulse signals on the homogeneous sensor, all cross-circuits
and connections to DC 24 V and DC 0 V can be detected.
PL d or higher according to EN 13849-1 can be achieved on:
- The usage of sensors / switching elements with positive actuation.
- The usage of 2 sensors / switching elements with independent actuation
- Ditto. However with actuation via a common actuating device in conjunction with a fault
exclusion for this device.
X14
I01
I02
I03
I04
.
.
.
I13
I14
T1
T2
X12
T1
T2
L+
L-
Figure: Homogeneous dual-channel sensor with test pulses
Safety instructions:
PL d or higher according to EN ISO 13849-1 is achieved on the usage of switching
elements / sensors with positive actuation
When using sensors with non-positively opening contacts or when using two
independent sensors with independent actuation, the macro (group) "Universal input
module" must be used in SafePLC2.
On the usage of common elements in the actuating chain, a fault exclusion is required
for these elements. The related restrictions and criteria according to EN 13849-1 are to
be met here.
HB-37350-810-01-38F-DE PSC1-C-10 Installation manual V1.1.docx
Version: 38F
Page 51 of 177