Installation manual
V_Ist
SOS_Result
Reset_In
Process value (speed) => no change to the output status on reset in the alarm state
Max. 3 sec
I1
Q =I1 AND I2
I2
IN_Result
Reset_In
Alarm_Status
Time-based function => reset the output status, triggering if limit exceeded again
Safety instructions:
For time-based functions, e.g. monitoring of the timing of complementary input signals,
the output status is reset and a state defined as erroneous only detected if the (time)
limit is exceeded again.
To protect against incorrect usage, e.g. repeated triggering of the reset function to
bypass an alarm state, if necessary applicative measures must be taken in the PLC
programming.
HB-37350-810-01-38F-DE PSC1-C-10 Installation manual V1.1.docx
Version: 38F
V_Ist > SOS_V_Max
Max. 3 sec
Max. 3 sec
Max. 3 sec
Max. 3 sec
Q =I1 AND I2
Q =I1 AND I2
Page 131 of 177