Figure: Single-channel switching output Q1_PP with dual-channel external circuit as
combination of electromechanical element and hydraulic/pneumatic valve monitoring on two
inputs
Safety instructions:
Only recommended to a limited extent for safety applications! On this topic see also the
information in EN 13849-1 on usage and the fault exclusions necessary.
For PL c and higher a signalling/warning device is required that immediately makes
clear the hazardous situation to the operator
With increased requirements it is to be noted that at least 1 switching process must
take place every 24 hours to test the ability of the external contactor to switch.