7.4.6 Replacing a T/H Sensor

Prerequisites
Context
Preparation: Maintain from the rear door.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the rear door and remove the air filter.
Step 3 Remove the cable terminals from the T/H sensor.
Step 4 Pull out the T/H sensor upwards.
Figure 7-9 Removing a T/H sensor (NetCol5000-C065)
Issue 06 (2022-12-15)
A T/H sensor needs to be replaced.
A spare T/H sensor of the same model is available and functional.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.