Connecting The Monitoring Network Cable; Connecting Fe Monitoring Network Cables (Snmp/Modbus-Tcp); Connecting Northbound Rs485 Monitoring Network Cables (Modbus-Rtu Protocol) - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Step 3 Secure the cables.
----End

4.14.4.4 Connecting the Monitoring Network Cable

The smart cooling product supports both RS485 and FE monitoring.

4.14.4.4.1 Connecting FE Monitoring Network Cables (SNMP/Modbus-TCP)

Figure 4-68 Connecting FE monitoring cables (Modbus-TCP)
Figure 4-69 Connecting FE monitoring cables (SNMP)
4.14.4.4.2 Connecting Northbound RS485 Monitoring Network Cables (Modbus-
RTU Protocol)
When the host monitors smart cooling products over northbound RS485 ports, it
takes 3 seconds to collect all data of a single smart cooling product. Therefore, the
time required for collecting data from
seconds. If the time required for the host to collect data of all smart cooling
products does not meet performance requirements, the smart cooling products
can be grouped for data collection. For example, if the host needs to collect data
of all smart cooling products within 12 seconds, it is recommended that every four
smart cooling products be divided into one group. Connect the COM-IN port on
the main control module of the first smart cooling product in each group to the
host.
Issue 06 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
N smart cooling products in a group is 3 x N
4 Installation
87