Correlation Relationship Of Parameters - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Step 2 Set parameters.
Parameter
WiFi SSID
WiFi password
Enable WiFi
WiFi group sharing
enable
Step 3 Tap Submit.
----End

5.5.5 Correlation Relationship of Parameters

When setting parameters, pay attention to the following relationships.
Alarm Parameters
Parameters of Teamwork Settings
Number of smart cooling products in this group ≥ Number of running smart
cooling products in this group
Issue 06 (2022-12-15)
Supply air high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Hot aisle low
temperature alarm threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Hot aisle low temperature
alarm threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Set WiFi SSID based on the actual configuration; WiFi
SSID is the name used for the WiFi hotspot over which
a mobile phone can connect to the smart cooling
product.
Enter the WiFi password when you use a mobile phone
to connect to the WiFi. The WiFi has no preset
password. When you enable the WiFi function for the
first time, you need to set a password.
Enables the WiFi function of the smart cooling product.
The default status is Disable.
When a mobile phone is connected to the WiFi of the
smart cooling product, it can access the units in the
same FE cascading network.
5 Power-On Commissioning
120

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents