Table 5-6 Description
Parameter
Indoor fan control type
Indoor fan silent mode
Indoor fan pressure
difference setpoint
Air-side difference
pressure sensor type
Min indoor fan speed
Max indoor fan speed
----End

5.5.3 Setting Teamwork Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Issue 06 (2022-12-15)
Teamwork group No.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data. The recommended value range is 1 to the number of
units in the group.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Sets the control type for
the indoor fan.
Set maximum speed of
indoor fan to reduce
equipment noise.
Sets the value for the
pressure difference
control.
Sets the measuring
range for the air side
differential pressure
sensor.
Sets the minimum speed
for the indoor fan.
Sets the maximum speed
for the indoor fan.
5 Power-On Commissioning
Setting Rule
Normally, retain R/S air
temp diff rate ctrl. If
the differential pressure
sensors are configured,
change to Pressure diff
ctrl.
You are advised not to
change the value.
The default value is 10
Pa. When there are
partial hot spots indoors,
you are advised to raise
the value to ensure that
the air volume of the
indoor fans is between
60%–70%.
There is no default value.
Set it to 0–50 Pa.
You are advised not to
change the value.
You are advised not to
change the value.