Connecting The T/H Sensor Outside The Cabinet - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Connect the other end of the water sensor cable to Water– and Water+ on the
water sensor at the signal port through the signal cable hole at the top of the
cabinet.
Step 3 Secure the cable to the left post of the cabinet using cable ties.
Figure 4-72 Installing a water sensor
Place the sheet metal of the water sensor upwards and its detection board
downwards on the ground.
----End

4.14.6 Connecting the T/H Sensor Outside the Cabinet

Context
T/H sensors outside the cabinet are configured to detect the temperatures of
cold/hot aisles. They can be flexibly installed on the server cabinet based on onsite
situation. It is recommended that the T/H sensors be deployed near heat sources
in the hot aisle, or in places which lacks cooling air in the cold aisle. The T/H
sensors outside the cabinet must be near the smart cooling product to sense the
temperature of the outlet air, and must be away from the air exhaust vents of
other smart cooling products
Procedure
Step 1 Connect the T/H sensors outside the cabinet and the T/H sensors at the air return
side in series.
Issue 06 (2022-12-15)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
89