Technical Specifications (Netcol5000-C030/C032) - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Item
Air volume (m
Maximum operating current
(A)
Maximum operating pressure
(MPa)
Humidification
Humidification capacity (kg/h)
External dimensions (H x W x
D)
Installation mode
Air filter level
Net weight (kg)
a: Rated working conditions are that the return air temperature is 37°C; the
return air relative humidity is 24% RH; the supply/return water temperatures are
10°C/15°C respectively; and the external static pressure of the smart cooling
product is 0 Pa.

3.3 Technical Specifications (NetCol5000-C030/C032)

Table 3-5 Technical specifications of NetCol5000-C030/C032
Item
Power system
Tolerance
Issue 06 (2022-12-15)
3
/h)
NetCol5000-C030
220 V AC to 240 V AC 1 Ph 50/60
Hz, dual power supplies
Rated voltage –15% to +10%,
rated frequency ±5 Hz
Copyright © Huawei Digital Power Technologies Co., Ltd.
NetCol5000-C065
10000
15
1.6
● NetCol5000-C065H90D0: No
● NetCol5000-C065H9HD0: Yes
● NetCol5000-C065H9HE0: Yes
● NetCol5000-C065H90D0: 0
● NetCol5000-C065H9HD0: 3
● NetCol5000-C065H9HE0: 3
2000 mm x 600 mm x 1200 mm
Installed on a raised floor or base; bottom pipe
routing. Top pipe and cable routing can also
be supported.
G4
● NetCol5000-C065H90D0: 222
● NetCol5000-C065H9HD0: 224
● NetCol5000-C065H9HE0: 224
NetCol5000-C032
220 V AC to 240 V AC 1 Ph
50/60 Hz, dual power
supplies
Rated voltage –15% to
+10%, rated frequency ±5
Hz
3 Product Specifications
32

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents