Warnings - Ingeteam INGECON SUN 1Play TL M Installation And Usage Manual

Hide thumbs Also See for INGECON SUN 1Play TL M:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 45
Ingeteam
Alarm
Lighting*
Orange,
FW update
constant
Grid consumption
Orange, 1
Low power PV conn.
Orange, 1
Overvoltage failure AC
Red, 4
Overvoltage failure DC
Red, 4
Power supply fault
Red, 1
Idc fed to grid
Red, 3
Setting change
Red, 1
Insulation alarm
Orange, 5
Saturation alarm Iac
Orange, 5
Low Vdc
Orange, 1
Shut-off due to
Orange,
burn-out
constant
* The number of flashes is indicated.

17.2. Warnings

Warning
Fan blocked
Possible fan blockage
Temperature above operating
High temperature
temperature
Temperature below operating
Low temperature
temperature
High Vdc
High DC input voltage
String box
Communication fault with the
communication
INGECON SUN String Control
Communication fault with the self-
Self-consumption
consumption devices (wattmeter
communication
or INGECON EMS Manager)
82
LED
Description
Inverter shutdown due to firmware
load
Grid consumption power out of the
permitted range
The generated power in the PV
array is not sufficient to connect to
the AC grid
Fault originating in the AC
overvoltage discharger
Fault originating in the DC
overvoltage discharger
Power supply fault to the
electronic circuit boards
DC current fed to the grid out of
the permitted range
Inverter setting change
Insulation resistance out of range
AC current saturation
Low DC voltage
Inverter shut off during the
burn-out test
Description
Normal shutdown due to inverter firmware update.
This may be due to a low irradiance level. Otherwise,
check the PV array.
Check the condition of the AC overvoltage
protection.
Check the condition of the DC overvoltage
protection.
Check the correct connection of the DC cables.
Open the unit and check the correct connection of
the control board.
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Normal shut down due to a change in the inverter
setting.
Search for an insulation fault in the PV array.
Check the installation in the AC part.
If the error persists, contact the Technical Service.
This may be due to a low irradiance level. Otherwise,
check the PV array.
Shut down occurred during the factory tests.
Check the condition of the fan and that there are no elements that
prevent it functioning properly.
Check the room temperature does not exceed the specified
maximum temperature and the inverter is not exposed to direct
sunlight. Also check the functioning of the fans.
Check the room temperature is not below the specified minimum
temperature.
Check the inverter connection with the INGECON SUN String Control.
If the error persists, contact the Technical Service.
Check the connection of the different elements. If the error persists,
contact the Technical Service.
ABE2011IQM01_ - Installation and usage manual
Troubleshooting
Solution
Solution