Unit description
DC input
Recommended power range of PV array
Maximum input voltage
(2)
Voltage range MPP1
(3)
Voltage range MPP2
(3) (4)
Operating voltage range
(4)
Minimum voltage for Pnom with DC inputs
in parallel
Maximum short circuit current
(input 1 / input 2)
Maximum inverter backfeed current to the
array
MPPT
Number of strings
Strings per MPP
Maximum input current
(input 1 / input 2)
Maximum input current per string
AC output
Nominal power (up to 45 ºC)
Maximum continuous power
Max. temperature for nominal power
Maximum current
Maximum transient current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Voltage range
Nominal frequency
Cosine of Phi
Adjustable cosine of phi
THD
Performance
Maximum efficiency
Euroefficiency
General data
Cooling system
Weight
Measurements (height x width x depth)
Stand-by current
(6)
Nocturnal current
Operating temperature
Relative humidity (without condensation)
Protection class
Markings
EMC and safety regulations
Grid connection regulations
Depending on the type of installation and geographical location.
(1)
temperatures.
The output power will be determined by the tension and current configuration selected at each input.
(3)
input must be at 125 V at least.
(5)
For each ºC of increase, the output power is reduced by 1.8 %.
ABE2011IQM01_ - Installation and usage manual
4.6TL M
5.2 ~ 6 kWp
(1)
850 V
125 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
216 V
13 / 13 A
0 A rms
2
2
1
11 / 11 A
11 A
4.6 kW
4.6 kW
58 ºC
(5)
26.2 A
26.2 A
30 A rms
230 V
122 ~ 265 V
50 / 60 Hz
1
Yes. Smax = 4.6 kVA
< 3 %
97.9 %
97.5 %
21 kg
< 10 W
0 W
–25 ~ +65 ºC
0 ~ 100 %
IP65
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-11, EN 61000-3-12, EN
62109-1, EN 62109-2, IEC62103, EN 50178, FCC Part 15, AS3100
RD1699/2011, DIN V VDE V 0126-1-1, EN 50438, CEI 0-21, VDE-AR-N 4105:2011-08, G59/2,
P.O.12.3, AS4777.2, AS4777.3, IEC 62116, IEC 61727, UNE 206007-1, ABNT NBR 16149, ABNT
NBR 16150, South African Grid code, Chilean Grid Code, Romanian Grid Code, Ecuadorian Grid
Code, Peruvian Grid code, IEEE 929, Thailand MEA & PEA requirements
Never exceed this value. Consider the voltage increase of the panels 'Voc' at low
(2)
5TL M
5.5TL M
5.7 ~ 6.5 kWp
6 ~ 6.8 kWp
850 V
850 V
125 ~ 750 V
125 ~ 750 V
90 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
90/125 ~ 850 V
234 V
258 V
13 / 13 A
13 / 13 A
0 A rms
0 A rms
2
2
2
2
1
1
11 / 11 A
11 / 11 A
11 A
11 A
5 kW
5.5 kW
5 kW
5.5 kW
55 ºC
50 ºC
26.2 A
26.2 A
26.2 A
26.2 A
< 30 A rms (60 ms)
30 A rms
30 A rms
230 V
230 V
122 ~ 265 V
122 ~ 265 V
50 / 60 Hz
50 / 60 Hz
1
1
Yes. Smax = 5 kVA
Yes. Smax = 5.5 kVA
< 3 %
< 3 %
98 %
98 %
97.6 %
97.6 %
Natural convection
21 kg
21 kg
470 x 360 x 180 mm
< 10 W
< 10 W
0 W
0 W
–25 ~ +65 ºC
–25 ~ +65 ºC
0 ~ 100 %
0 ~ 100 %
IP65
IP65
CE
(6)
Current from PV array.
Ingeteam
6TL M
6.3 ~ 7 kWp
850 V
125 ~ 750 V
90 ~ 750 V
90/125 ~ 850 V
281 V
13 / 13 A
0 A rms
2
2
1
11 / 11 A
11 A
6 kW
6 kW
45 ºC
26.2 A
26.2 A
30 A rms
230 V
122 ~ 265 V
50 / 60 Hz
1
Yes. Smax = 6 kVA
< 3 %
98 %
97.6 %
21 kg
< 10 W
0 W
–25 ~ +65 ºC
0 ~ 100 %
IP65
To lower it to 90 V the other
(4)
51
DE
EN
ES
FR
IT
PT

Advertisement

Table of Contents
loading

Table of Contents