Regenerative Operation At Parallel Operation Of Combivert R6-S With Decoupling Diodes - KEB COMBIVERT R6 Instruction Manual

Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

Connection Power Unit
4.4.7 Regenerative operation at parallel operation of COMBIVERT R6-S with decoupling
diodes
Regenerative inverter currents > current of one R6-S
1
L1
L2
L3
PE
1
Mains fuse
2
Mains contactor
2a Regenerative contactor
3
Mains fuse type gR
4
HF filter
1)
A mains choke with uk=4 % is mandatory required for reduction of circulating currents.
2)
The cable cross‑section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise there are fuses
in the DC link circle (10) necessary The indicated maximum protection for the connected frequency inverters must be observed !
3)
If the inverter current > current of the COMBIVERT R5‑S it must be wired at an external terminal (12).
4)
The regenerative contactor may only be connected if the precharging in the DC link circle of the inverter is completed. If the precharging of R6‑S
and frequency inverter is in the same DC branch, regenerative contactor are eventually not necessary (depending on the charging resistors
and the DC link capacity).
5)
Parallel connection of the frequency inverter and R6‑S causes a circulating current in regenerative operation. It is depending on the inductance
of the mains choke. The entire regenerative power is 75... 90 % of the R6‑S regenerative power.
6)
In case of parallel connection of R6‑S the total power can be smaller up to 15 % caused by production tolerances of the commutation choke. The
impedance voltages uk of the commutation chokes must be the same in case of parallel connection of R6‑S with different sizes.
GB - 22
4
3
L1
L1'
L2
L2'
L3
L3'
2a
4
3
L1
L1'
L2
L2'
L3
L3'
12
2
4
L1
L1'
L2
L2'
L3
L3'
5
Commutation choke
6
Mains choke
7
COMBIVERT R6-S
4)
8
Inverter with DC output
7
X2B
X2B
5
L12
L1.1
L1.2
L2.1
L2.2
L22
L3.1
L3.2
L32
PE
X2B
X2B
5
L12
L1.1
L1.2
L2.1
L2.2
L22
L32
PE
L3.1
L3.2
6
PE
L1
8
L2
L3
9
6
PE
L1
8
L2
L3
9
5) 6)
10 DC fuses type aR/gR
1) 5)
11 DC fuses type aR/gR
12 External terminal
13 Decoupling diodes (see annex)
++
++
13
- -
- -
7
++
++
13
12
- -
- -
10
- -
-
PE
11
- -
-
PE
9
Motor
3)
2)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert r6-s

Table of Contents