KEB COMBIVERT R6 Instruction Manual page 35

Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

No.
Name
CP.33
Operating mode
This parameter determines the master or slave of regenerative units at parallel connection.
Further it is adjusted whether a harmonic filter or a commutation choke is series-connected.
Single units must be adjusted to master.
Value range
0
1
2
3
No.
Name
CP.34
Regeneration level
Value range
100...120 %
Meaning
Master with commutation choke
Master with harmonic filter
Slave with commutation choke
Slave with harmonic filter
Meaning
The regeneration level determines the starting value to energy regenera-
tion. The adjusted value refers to the reference value of the DC voltage
in percentage. The status changes from Standby „Stb" to regeneration
„rEGEn".
Operation of the Unit
r/w
yes
r/w
yes
Enter
Origin
yes
Pn.19
Enter
Origin
cS.02
GB - 35