Maintenance; Trouble Shooting - Pylontech Force-H2-V2 Manual

Lithium phosphate energy storage system
Table of Contents

Advertisement

5.

Maintenance

5.1 Trouble Shooting:

Danger: The Force-H2-V2 is a high voltage DC system, operated by qualified and
authorized person only.
Danger: Before check the failure, must check all the cables connection and the BESS
system can turn on normally or not.
Check the environment first
No
Problem
No power output, no
1
led on.
After turned on,
status LED slow
2
flashing orange.
Others off.
Status LED fast
3
flashing orange,
others off.
4
Buzzer rings continue Relay adhesion or failure.
5
Status LED solid
Possible Reason
Press start button too short.
The button battery in controller
is missing or failure.
The power supply in controller
is failure
The battery voltage is too low.
The connector of base is failure
Self-checking failure.
DC side has a voltage, but
voltage difference with the
battery system is higher than
20V.
BMS internal failure.
The time interval after last time
black start is too short.
The battery system under error
condition such as: temperature
or current protection or other
error, thus do not response
black start.
Communication lost with
37
Solution
To turn on, at least 5s
To black start, at least
10s.
Change the controller
module.
Make sure at least 2
battery modules.
The base is not
connected or change the
base
Make sure no DC voltage
or set correct DC voltage
before press start button.
Then follow turn on
process.
Use debug tool to further
analysis or change the
controller module.
Wait more than 5 minutes
and try black start again.
Make sure no other
protection factor. Or use
debug tool to further
analysis.
Completely disconnect
battery system with any
DC source then make a
restart. If problem remain,
then swap the controller.