Pylontech Force-H2-V2 Manual page 18

Lithium phosphate energy storage system
Table of Contents

Advertisement

Power Switch
ON: main breaker ON, able to turn on battery system by start button.
OFF: system turn off completely, no power output.
Caution: When the breaker is tripped off because of over current or short circuit,
must wait more than 30min then can turn on it again, otherwise may cause the
breaker damage.
Start
Start function: press more than 5sec until
the buzzer rings, to turn on controller.
Multi-groups start up sequence: please start up the last string (from communication
structure, the last slave) of battery system first, one by one to the first string which
shall be start up lastly. Details as below table
Communication Structure
Master string
Slave string 1
Slave string 2
Slave string 3
Slave string 4
Slave string 5
Black start function: when system turn on, and relay is OFF, press more than 10sec, and
relay will turn on for 10 min without communication (depends on conditions).
Start-up Sequence
Last Start up
5th Start up
4th Start up (if has)
3rd Start up (if has)
2nd Start up (if has)
1st Start up (if has)
14

Advertisement

Table of Contents
loading

Table of Contents