Sinclair S therm Series Service Manual page 95

Split heat pumps
Table of Contents

Advertisement

[Notes]
●This function is allowed only when the unit has just repowered and not turned on. For the unit which once has
been put into operation, this function is unavailable, alerting "Wrong operation".
●This function will not be memorized upon power failure.
3.2.4.17 Control Logic of the Water Tank Heater
[Operation Instructions]
At the commissioning parameter setting page, by touching "Tank heater", it will access to the setting page of
control logic for the water tank heater.
[Notes]
●"Reserved" will be displayed when the water tank is unavailable.
●This setting can be done only when the unit is off.
●This function can be memorized upon power failure.
●Logic 1: NEVER allowed the Unit's Compressor and the Water Tank Electric Heater or the Optional Electric
Heater to work at the same time.
●Logic 2: While Heating/ Cooling + Hot water mode (Hot Water priority) Tset ≥ THPmax + ΔThot water +2, when
water tank temperature reach THPmax, the water tank EH will be ON and start to do hot water, at the same time,
the compressor wil turn to heating/cooling mode, water tank EH and Compressor will be ON together.
3.2.4.18 Gate Control Memory
[Operation Instructions]
At the commissioning parameter setting page, by touching "Gate-Ctrl Memory", it will access to the setting
page.
[Notes]
●When it is enabled, "Gate-Ctr" will be memorized upon power failure.
●When it is disabled, "Gate-Ctr" will not be memorized upon power failure.
3.2.4.19 Parameter Setting
[Operation Instructions]
At the commissioning parameter setting page, by touching "PARAM.", it will access to the pages as shown
below.
Page of Commissioning Parameters
At this page, select the desired option and then go to the corresponding page.
After that, by pressing "OK", this setting will be saved and then the unit will run based on this setting; or by
91