3.2.4.8 Remote Sensor
[Operation Instructions]
At the commissioning parameter setting page, by touching "Remote sensor", the control panel will access to the
corresponding setting page, where it can be set to "With" or "Without".
[Notes]
●This setting will be memorized upon power failure.
●Only when "Remote sensor" is set to "With", the "Ctrl. State" can be set to "T-room".
3.2.4.9 Air Removal
[Operation Instructions]
At the commissioning parameter setting page, by touching "Air removal", the control panel will access to the
corresponding setting page, where it can be set to "On" or "Off".
[Notes]
●This setting will be memorized upon power failure.
●This setting can be done only when the unit is turned off. And when it is set to "On", the unit is not allowed to
be turned on.
3.2.4.10 Floor Debug
[Operation Instructions]
1.At the commissioning parameter setting page, by touching "Floor debug", the control panel will access to the
corresponding setting page.
2.At the setting page, "Floor debug", "Segments", "Period 1 temp", "Segment time", and "ΔT of segment"
can be set.
No.
Full Name
1
Floor debug switch
2
Quantity of segments
Temperature of the first
3
segment
4
Duration of each segment
Displayed Name
Floor debug
Segments
25~35°C/
Period 1 temp
77~95°F
Segment time
12~72 hours
88
Range
Default
On/Off
Off
1~10
1
25°C/
77°F
0
Accuracy
/
1
1°C
12 hours