Table 5-1: Diagnostic Message Troubleshooting
LCD display messages Host diagnostic
FLOW CONFIG
FLOW INCOMP ERROR
FLOW INCOMP ERROR
FLOW INCOMP ERROR
FLOW LIMIT
Emerson.com/Rosemount
Possible problems
message
Updating Flow
A flow configuration is
Configuration - Flow
currently being
Values Constant
downloaded to the
transmitter. During the
download, the flow
output will be fixed at
the last calculated
value. Once the
download is complete
the transmitter will
resume live
calculations.
Energy Invalid for Flow
The energy flow
Configuration
variable is not
compatible with the
current flow
configuration but is
mapped to the
totalizer, a process
variable, or a burst
variable.
Static Pressure Sensor
A static pressure
Missing
sensor is needed for
the current flow
configuration.
Flow Configuration
The flow configuration
Download Error
did not successfully
download to the
transmitter.
Flow Output Out of
The flow output value
Limits
is exceeding the flow
rate operating limits.
Troubleshooting
(continued)
Recommended
actions
No action is required.
Wait until the flow
configuration
download is complete
before performing
other configuration
tasks.
These discrepancies
can be fixed with the
following actions:
Verify configuration for
the fluid type supports
Energy Flow
calculation.
Do not specify energy
flow for the totalizer,
process variables or
burst variables unless
the transmitter has a
compatible flow
configuration.
Download a flow
configuration that is
compatible with the
sensors equipped in
the device or replace
the module with a
model that includes a
static pressure sensor.
Re-download the flow
configuration using the
Engineering Assistant
software.
Verify the process
conditions, and modify
the flow configuration
parameters and
operating ranges as
needed.