Configuration
October 2018
Figure 2-37: Variables - Static Pressure Tab
Under the Static Pressure Setup heading, edit the Absolute Pressure Units and Gage
Pressure Units as needed. The static pressure Damping may also be edited.
Note
The transmitter may be equipped with either an absolute or gage static pressure sensor
type depending on specified model code. The type of static pressure sensor equipped in
the transmitter can be determined by referring to the Static Pressure Sensor Type heading.
The static pressure type not being measured is a calculated value using the atmospheric
pressure value as specified under the User-Defined Atmospheric Pressure heading.
The Sensor Limits and Minimum Span for the absolute and gage static pressure can be
viewed under the Sensor Limit headings.
2.7.6
Process temperature
Mass and energy flow Fast Keys
Direct process variable output Fast Keys
Note
For process teperature sensor calibration, see
transmitter was ordered with Fixed Process Temperature Only, the Fixed Temperature
Value and Units can be edited on the Fixed Temperature tab.
58
1, 4, 1, 6
1, 4, 1, 3
Process temperature sensor calibration
Rosemount 3051S Multivariable Transmitter
Reference Manual
00809-0100-4803
. If a