the
selection keys:
•
[Clear Alarms] - Selecting this key will clear all
alarms and/or shutdowns from this screen.
•
[Alarms/Shutdown History] - A full screen of failures
is stored, along with the Last Fail Date/Time of the
failure.
The
stored
"Alarms/Shutdowns History" screen. The data is
saved, even if there is a power outage.
To resume normal operation it will be necessary to go
through the following steps:
1.
Correct the conditions causing the alarm.
FRICK QUANTUM CONTROL PANEL
ACUair OPERATION
MAIN MENU SELECTION -
"ALARMS/SHUTDOWNS" SCREEN
"Alarms/Shutdowns"
screen
data
shows
on
2.
To clear or reset the "Alarms/Shutdowns" screen and
turn off any alarm annunciation device, from the
screen press the [Clear Alarms] key. This will also
clear the "ALARM" or "SHUTDOWN" message from
the "Operating Status" screen.
3.
If the conditions causing the alarm have not been
corrected or a new fault has occurred, a new
the
"ALARM" or "SHUTDOWN" message will appear. The
Alarms/Shutdowns history screen keeps a record of
the alarms and shutdowns. This information will help
troubleshoot persistent operational problems.
Refer to the "Alarms/Shutdowns Message" section
for a list of all the possible alarms.