S90-500 CS/JULY 2002
File:
SERVICE MANUAL - SECTION 90
Replaces:
S90-500 CS/APR 2001
Dist:
3, 3a, 3b, 3c
COMMUNICATIONS SETUP
®
FRICK
QUANTUM™
®
ACUair
CONTROL PANEL
VERSION 2.1x

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUANTUM ACUair and is the answer not in the manual?

Questions and answers

Summary of Contents for Frick QUANTUM ACUair

  • Page 1 S90-500 CS/JULY 2002 File: SERVICE MANUAL - SECTION 90 Replaces: S90-500 CS/APR 2001 Dist: 3, 3a, 3b, 3c COMMUNICATIONS SETUP ® FRICK QUANTUM™ ® ACUair CONTROL PANEL VERSION 2.1x...
  • Page 2: Table Of Contents

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 2 COMMUNICATIONS SETUP Table of Contents QUANTUM™ IDENTIFICATION ..........................4 Setting Up The Quantum™ For Communication.....................4 Com-2 Pinouts For Quantum™ 3......................4 Com-2 Pinouts For Quantum™ 4......................4 RS-232 Communications ..........................5 Quantum™ 3 ............................5 Quantum™...
  • Page 3: Communications Setup

    Any modification to the standard default settings may have a severe negative impact on the operation and performance of the ® equipment. Any modification to these control settings is the sole responsibility of the user/owner and Frick disclaims any liability for the consequences of these modifications. It is possible that the modification of these settings may cause improper operation and performance that results in property damage, personal injury or death.
  • Page 4: Quantum™ Identification

    Data communication to and from the Quantum™ can be development. Because of the ever-increasing speed, through a modem, remote data communications terminal, ® memory, features, and power of microprocessors, Frick programmable controller, or leader computer via either Controls will continue to introduce the latest advancement RS-422,...
  • Page 5: Rs-232 Communications

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 5 RS-232 Communications NOTE: Refer to the manual that comes with the AC7A/B card for specific jumper information (as the configuration Following is the pin connections showing how to wire a...
  • Page 6: Change Communications" Screen

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 6 COMMUNICATIONS SETUP After verifying both the Converter card and Quantum™ We have used both an Opto 22 AC7A/B and an Opto 22 jumper settings, the interconnecting wiring must be done.
  • Page 7: Protocol Description

    Therefore, you should • If the TX2 is not blinking then check the ® consult Frick Controls for the exact details on your communication protocol setup at the panel, particular unit(s) before developing system software to the panel’s ID and the Com-2 baud rate...
  • Page 8: Frick Protocols

    Frick Protocols types: ® All commands for Frick protocols must be in ASCII to be COMMAND CODE and DESCRIPTION recognized. The data should be setup as an 8 bit Word with either no Parity or even Parity, and a Stop Bit. The F1 = Alarms/Shutdowns Annunciation Page 1.
  • Page 9 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 9 RETURN Alarms & Shutdowns - Page 2 data: RETURN Alarms & Shutdowns - Page 3 data: $01F2 $01F3 Start of command sequence. Start of command sequence. Quantum ID code.
  • Page 10 Frick Table address of the setpoint. Return the value of a Table address. Checksum 0000 Frick Address of first data value in Table Carriage Return Number of subsequent values to return (up to 25 values can be requested) RETURNED ANSWER, “A” followed by the “ID”, Checksum and 1 “CR”, “LF”...
  • Page 11 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 11 RETURN Unit Status - Units1-4 data: $01IA RETURN Unit Status - Units1-4 data: $01Z1 Start of command sequence. Start of command sequence. Quantum ID code. Quantum ID code.
  • Page 12: Conversion Chart For Decimal / Hexadecimal / Ascii

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 12 COMMUNICATIONS SETUP CONVERSION CHART FOR DECIMAL / HEXADECIMAL / ASCII Decimal Hexadecimal Decimal Hexadecimal Decimal Hexadecimal ASCII ASCII ASCII (DEC) (HEX) (DEC) (HEX) (DEC) (HEX) ctrl @ NUL ctrl A SOH...
  • Page 13: Allen-Bradley Communication

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 13 Allen-Bradley Communication remote stations can format reply packets faster than others. To provide for the reading and writing of data to Message Timeout - Defines the amount of time in Quantum™...
  • Page 14: Write Message Setup Example

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 14 COMMUNICATIONS SETUP Write Message Setup Example Channel Configuration Read/Write Message Channel 0 = System (Leader) for half-duplex or System Type: Peer-To-Peer (Point-To-Point) for full-duplex Read/Write: Write Remote Mode Change: DISABLED...
  • Page 15: Allen-Bradley Programming Overview

    Page 15 Allen-Bradley Programming Overview Channel Configuration This section contains programming examples for reading The following are representations of the channel ® data from, and writing data to the Frick Quantum™ configuration screens from RSLogix500 control panel from an Allen Bradley (AB) SLC500 or PLC5 programming software for the SLC500.
  • Page 16: Message Sequence Logic

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 16 COMMUNICATIONS SETUP Message Sequence Logic message to the Quantum™ panel. This logic prevents hang up due to lost communications or message errors. Use the following logic to sequence read and write...
  • Page 17: Message Read Setup Screen

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 17 Message Read Setup Screen register and place them into the SLC500’s N10:1 through N10:28 register. The following setup screen is programmed to obtain 28 consecutive data files from the Quantum™ (ID#1) N10:1 •...
  • Page 18: Message Write Logic

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 18 COMMUNICATIONS SETUP Message Write Logic modify the control block and setup screen parameters accordingly. Use the following logic to write data from the Quantum™ panel. To write more data or to write data to several...
  • Page 19: Message Write Setup Screen

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 19 ® Message Write Setup Screen ACUair mode to the Quantum™ (ID#1) N55:3 data file from the SLC500’s N55:3 data file. The following setup screen is programmed to write the •...
  • Page 20: Modbus Protocol

    00 to FF hexadecimal. These are with one read request. to be made from a pair of ASCII characters. The data field of messages sent from a Leader to the ® Address references are numbered relative to the Frick Quantum™ devices contains additional addresses in the Quantum™...
  • Page 21: The Response

    Unit 1 Outside Air byte, containing an eight-bit binary value. The LRC value ® Temperature Analog Input. In this case, it would be Frick is calculated by the transmitting device, by adding together Address 158 (decimal). Since this is the only address we...
  • Page 22 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 22 COMMUNICATIONS SETUP The first part of the message will be a Colon ( : ). This 158 decimal equals 9E hex. Looking at our example, we represents a “heads up” alert that data is coming “down see that we need a H.O.
  • Page 23: Write Example

    “Unit 1 Write Function ® H.O. address (hex) Process Control Setpoint”. In this case, it would be Frick L.O. address (hex) Address (decimal). Since this is the only address we are H.O. # of Data Value interested in writing to, send the following message: L.O.
  • Page 24: Response Example

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 24 COMMUNICATIONS SETUP The value that we wish to send is 25.0 (250). Our Data After the entire data packet has been created, simply Value part of the data packet is looking for a High and a press the [Enter] key, a Line Feed will automatically be Low Order value.
  • Page 25: Notes

    Start of Message by “1” (one). For instance, if you wanted to look Quantum™ ID # ® at Frick Address 135, you may need to actually Read Function look at address 136. The Quantum™ addressing Number of Bytes Returned...
  • Page 26: Hyperterminal

    “New Connection”. Type in panel setup, and cabling) are properly met so that ® whatever name you would like to use, “Frick ” communications may be established quickly with the was used in this example. This name will also Quantum™, so that time is not lost in trying to...
  • Page 27 Set the five boxes as follows, then click [OK]. the next is the “Data Bits ” box. For Modbus, you would ® want to use 7 data bits, for Frick and Quantum™ • Bits per second: 9600 (must match the protocols, use 8 data bits.
  • Page 28 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 28 COMMUNICATIONS SETUP The following screen will appear. This is the screen sent, the connected device recognizes and responds to whereby all communications (out of the computer, and into that data, and a response will be shown below the sent it) will be shown.
  • Page 29 To do this, click on the [ASCII documentation as presented here, for everything to look Setup…] button. ® On the ASCII Setup screen, for best results, check the For Frick protocols (# and $): boxes according to the following chart: • Echo typed characters locally For Modbus: •...
  • Page 30 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 30 COMMUNICATIONS SETUP The Properties screen will once again be shown. Click on the [OK] button to proceed. You will now be back to the main Hyperterminal computer (from the Quantum™), will appear on this communications screen.
  • Page 31: Testing Communications

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 31 Testing Communications be typed). Type in the following command: #01I, then press [ENTER]. (This command will request Set the keyboard for “CAPS” (so that all capital letters will Quantum™...
  • Page 32 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 32 COMMUNICATIONS SETUP The “Service Screen” will appear. Press the [Show Comms] key at the top right of the screen to view the communications information. • You will now be viewing all of the communications Quantum™...
  • Page 33: Quantum™ Data Table

    Modbus Address as shown in the following tables. the values are transferred between the Quantum and GCU These addresses should work for most applications. ® board. Setpoints whose Frick addresses are in the...
  • Page 34 N10:22 40023 Number of minutes before Screen Saver enabled ® N10:25 40026 External Communications through Comm 1 0 = Frick 1 = AB 2 = Modbus ® N10:26 40027 External Communications through Comm 2 0 = Frick 1 = AB...
  • Page 35 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 35 Unit 1 Settings: ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N10:100 40101 Unit 1 ID N10:114 40115 Unit 1 Cooling Demand...
  • Page 36 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 36 COMMUNICATIONS SETUP Unit 1 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N10:152 40153 Unit 1 Burner Analog Output 0 - 100%...
  • Page 37 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 37 Unit 1 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N15:30 40281 Unit 1 Cooling Setup 0 = Disabled 1 = Single Stage...
  • Page 38 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 38 COMMUNICATIONS SETUP Unit 1 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only N15:59 40310 Unit 1 Process Control Setpoint N15:61 30312 Unit 1 Cooling Command Proportional Band...
  • Page 39 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 39 Unit 1 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only N15:147 40398 Unit 1 Dehumidification Proportional Band N15:148 40399 Unit 1 Dehumidification Dead Band...
  • Page 40 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 40 COMMUNICATIONS SETUP Unit 1 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only N15:237 40488 Unit 1 Auxiliary Analog Input 4 N15:238 40489 Unit 1 Analog Auxiliary Output 1...
  • Page 41 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 41 Unit 2 Settings: ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N16:100 40601 Unit 2 Id N16:114 40615 Unit 2 Cooling Demand...
  • Page 42 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 42 COMMUNICATIONS SETUP Unit 2 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N16:156 40657 Unit 2 Variable Speed Fan Analog Output 0 - 100%...
  • Page 43 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 43 Unit 2 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only N17:31 40782 Unit 2 Heating Setup 0 = Disabled 1 = Single Stage...
  • Page 44 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 44 COMMUNICATIONS SETUP Unit 2 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only N17:59 40810 Unit 2 Process Control Setpoint N17:61 40812 Unit 2 Cooling Command Proportional Band...
  • Page 45 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 45 Unit 2 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only N17:120 40881 Unit 2 Cleanup Pre-Heat Lockout N17:121 40882 Unit 2 Cleanup Pre-Heat CV Maximum...
  • Page 46 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 46 COMMUNICATIONS SETUP Unit 2 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only N17:233 40984 Unit 2 Auxiliary Analog 1 N17:234 40985 Unit 2 Auxiliary Analog Input 1...
  • Page 47 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 47 Unit 3 Settings: ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1100 N18:100 41099 Unit 3 Id 1114 N18:114 41115 Unit 3 Cooling Demand...
  • Page 48 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 48 COMMUNICATIONS SETUP Unit 3 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1153 N18:153 41154 Unit 3 Heat Profile Analog Output 0 - 100%...
  • Page 49 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 49 Unit 3 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1280 N19:30 41281 Unit 3 Cooling Setup 0 = Disabled...
  • Page 50 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 50 COMMUNICATIONS SETUP Unit 3 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only 1309 N19:59 41310 Unit 3 Process Control Setpoint 1311 N19:61 41312 Unit 3 Cooling Command Proportional Band...
  • Page 51 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 51 Unit 3 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only 1380 N19:120 41381 Unit 3 Cleanup Pre-Heat Lockout 1381 N19:121 41382 Unit 3 Cleanup Pre-Heat CV Maximum...
  • Page 52 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 52 COMMUNICATIONS SETUP Unit 3 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only 1482 N19:232 41483 Unit 3 Digital Auxiliary 2 1483 N19:233 41484 Unit 3 Analog Auxiliary 1...
  • Page 53 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 53 Unit 4 Settings: ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1600 N20:100 41601 Unit 4 Id 1614 N20:114 41611 Unit 4 Cooling Demand...
  • Page 54 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 54 COMMUNICATIONS SETUP Unit 4 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1653 N20:153 41654 Unit 4 Heat Profile Analog Output 0 - 100%...
  • Page 55 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 55 Unit 4 Settings (Continued): ® Frick Modbus Read Description of Data Value Codes Address Address Address Only 1780 N21:30 41781 Unit 4 Cooling Setup 0 = Disabled...
  • Page 56 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 56 COMMUNICATIONS SETUP Unit 4 Setpoints: ® Frick Modbus Read Description of Data Address Address Address Only 1809 N21:59 41810 Unit 4 Process Control Setpoint 1811 N21:61 41812 Unit 4 Cooling Command Proportional Band...
  • Page 57 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 57 Unit 4 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only 1880 N21:120 41881 Unit 4 Cleanup Pre-Heat Lockout 1881 N21:121 41882 Unit 4 Cleanup Pre-Heat CV Maximum...
  • Page 58 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 58 COMMUNICATIONS SETUP Unit 4 Setpoints (Continued): ® Frick Modbus Read Description of Data Address Address Address Only 1982 N21:232 41983 Unit 4 Digital Auxiliary 2 Type 1983 N21:233 41984...
  • Page 59 Data values select 0=x10 1=x100 0 & 1 ® Note: Caution must be used when writing data to these Command addresses. It is not recommended to use Frick address 5012 for any purpose other than remotely displaying Pressure and Temperature data. SPECIAL (read only):...
  • Page 60 Quantum™ is capable of displaying the most recent 18 alarms, as well as the hour, ® minute and date that each alarm occurred. Each alarm is now accessible independently. For instance, reading Frick Address 4600 will return the value of the most recent alarm code. This code value will correspond to the ALARMS/SHUTDOWNS MESSAGE CODE near the back of the Communications Setup manual.
  • Page 61 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 61 Alarm List 2 - continued: Modbus Description of Data Address Address 4637 N25:137 Unit 1 Alarm # 8 Min. 4638 N25:138 Unit 1 Alarm # 8 Date High Order...
  • Page 62 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 62 COMMUNICATIONS SETUP Alarm List 2 - continued: Modbus Description of Data Address Address 4683 N25:183 Unit 1 Alarm # 17 Date High Order 4684 N25:184 Unit 1 Alarm # 17 Date Low Order...
  • Page 63 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 63 Alarm List 2 - continued: Modbus Description of Data Address Address 4739 N25:239 Unit 2 Alarm # 8 Date Low Order 4740 N25:240 Unit 2 Alarm # 9 Message...
  • Page 64 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 64 COMMUNICATIONS SETUP Alarm List 2 - continued: Modbus Description of Data Address Address 4785 N26:35 Unit 2 Alarm # 18 Message 4786 N26:36 Unit 2 Alarm # 18 Hrs.
  • Page 65 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 65 Alarm List 2 - continued: Modbus Description of Data Address Address 4841 N26:91 Unit 3 Alarm # 9 Hrs. 4842 N26:92 Unit 3 Alarm # 9 Min.
  • Page 66 ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 66 COMMUNICATIONS SETUP Alarm List 2 - continued: Modbus Description of Data Address Address 4887 N26:137 Unit 3 Alarm # 18 Min. 4888 N26:138 Unit 3 Alarm # 18 Date High Order...
  • Page 67 ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 67 Alarm List 2 - continued: Modbus Description of Data Address Address 4943 N26:193 Unit 4 Alarm # 9 Date High Order 4944 N26:194 Unit 4 Alarm # 9 Date Low Order...
  • Page 68: Alarms/Shutdowns Message Codes

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 68 COMMUNICATIONS SETUP Alarms/Shutdowns Message Codes 0000 No Alarm 0023 High Room Pressure Shutdown 0001 Outside Air Temp. Sensor Fault 0024 GCU Board Comm 2 Failed 0002 Discharge Air Temp. Sensor Fault...
  • Page 69: Quantum™ 3 Main Board History And Identification

    This “daughter board” can be easily identified by ® Quantum™ 1, 2 , 3 or 4. Additionally, Frick will request the presence of a large black heat sink mounted on the the Sales Order number, and the Operating System main processor chip.
  • Page 70: Quantum™ 3 Communications Jumpers

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 70 COMMUNICATIONS SETUP Quantum™ 3 Communications Jumpers LK25 FLASH MEMORY HEAT SINK SOCKET Display Cable LK11 LK10 COM1 This assembly is shipped with LK24 LK11 set to position “B”. If a...
  • Page 71: Quantum™ 4 Main Board History And Identification

    Quantum™ 1, 2, 3 or 4 (Quantum™ 3 is described in the of a “piggy back” daughter board mounted to the main ® previous section). Additionally, Frick will request the board. This “daughter board” is the communications Sales Order number, and the Operating System version portion of the Quantum™, and it can be identified by the...
  • Page 72: Quantum™ 4 Communications Jumpers

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 72 COMMUNICATIONS SETUP Quantum™ 4 Communications Jumpers Flash Card Socket (Located under board) Power PL11 Cable COM-2 COM-1 2 3 4 2 3 4 RS-422 PL12 RS-422 PL10 +5VDC COM-2...
  • Page 73: Customer Remote Computer/Dcs Rs-485 Communications

    ® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 CS COMMUNICATIONS SETUP Page 73 WIRING DIAGRAM – QUANTUM™ TO CUSTOMER REMOTE COMPUTER/DCS RS-485 COMMUNICATIONS COM2 COM2 COM2 (TB2) (TB2) (TB2) Belden #8761 Belden #8761 Belden #8761 To Customer #22 AWG or Equal...
  • Page 74: Connections

    ® ® S90-500 CS FRICK QUANTUM™ ACUair CONTROL PANEL Page 74 COMMUNICATIONS SETUP CONNECTIONS...
  • Page 75: Index

    COMMUNICATIONS SETUP Page 75 Index Frick®…….2, 3, 7, 15, 23, 29, 33, 34, 35, 36, 37, 38, 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 50, 51, 52, 53, 54, 55, 56, 57, 58, 59, 60, AB Protocol ............15 Address .......
  • Page 76 Protocol ....6, 20, 21, 25, 26, 27, 31, 32, 33 Allen-Bradley DF-1 serial ......... 6 Description............6 Serial..............20 Frick ..............6 Setting up Hyperterminal ........ 26, 32 ModBus ASCII serial ........6 Setting Up the Quantum™ for Communication..3 Setting Up Communication....... 6 Show Comms screen..........31...

Table of Contents