Horizontal Termination

Minimum vertical rise from the vent collar is a 24"
section vent pipe. See fig. 6.5. Minimum horizontal run
is 12" with natural gas and 18" with propane.
A maximum of two 90° or four 45° elbows may be used
in a horizontal termination. Whenever possible, use 45°
elbows instead a 90° elbow as they offer less restriction
to the flow of flue gases and intake air. Reduce the
overall horizontal run by 5 feet for each additional
elbow, whether 45° or 90°.
Snorkel Termination - ( 14" or 36"):
NATURAL GAS ONLY. DO NOT USE SNORKEL
TERMINATION WITH PROPANE FUEL.
A horizontal vent run may be made with a 90° elbow
directly to the rear of the stove only when terminated
by a 14 or 36 inch snorkel cap. Fig. 6.6 shows the
minimum vent pipe requirements.
14" Snorkel: The maximum horizontal vent run must not
exceed a 24" section of pipe and must be a minimum of
12".
36" Snorkel: The maximum horizontal vent run must not
exceed 5 feet and must be a minimum of 12".
The termination cap must not be recessed into the wall
or siding. Do not fill air space in wall around termination cap
with any type of insulation.
Wall Cut-out: A minimum 10" X 10" square hole is
adequate for proper pipe clearance through a wall,
provided the vent is positioned to maintain 2" minimum
clearance at the top. A 1" minimum clearance must be
maintained to combustible material around the other
sides. See fig. 6.7.
Any horizontal run of vent must have a 1/4" rise for
every foot of run toward the termination cap.
All horizontal terminations must comply with the clearance
specifications to adjacent structures as indicated in fig. 6.8.
Installation of a Vinyl Siding Standoff is required to
prevent damage to vinyl siding between the vent cap and
the exterior wall.
A horizontal termination cap must maintain a 3" clearance
to any overhead combustible projections that are 2 1/2" or
less. It must also maintain a 12" clearance from projections that
exceed 2 1/2". See fig. 6.9.
Vinyl siding projections require a default clearance of 18" to the
vent terminal.
A vent shall not terminate where it could cause
hazardous frost or ice accumulations on adjacent
property surfaces.
10
Figure 6.5. Minimum vent
pipe sections required for
horizontal termination:
A = 12" with NG
18" with LP
24”
74 1/2”
Figure 6.6. Minimum vent pipe
sections required for a 14" Snorkel
termination - Natural Gas ONLY.
.
52”
Minimum Vent into
14” Snorkel Termination
Figure 6.7. Install a listed
wall thimble according to
manufacturer's instruc-
tions to maintain required
clearance to combustible
materials.
A
Listed Wall
Thimble
14”
12”
Listed Wall
Thimble
NG
ONLY