In this normal case of use, it is not necessary to connect the exhaust duct to the open air.
In the opposite case, the exhaust duct must be connected to the open air, by the shortest way, and with as few bents
as possible.
Incline the flexi-hose downwards, as compared to the machine.
Protect the end of the exhaust duct from the bad weather.
Do not connect the exhaust duct to a gas, coal, fuel oil furnaces chimney. Separate it also from any other ducting
(tumble dryer, finishing cabinet).

4.5 Electric power supply :

The feeder cable sections mentioned in our literature are given only as a guide .
To obtain a value perfectly suited to your own application and which takes account of the different correction factors
in respect of your plant, refer to the tables below.
4.5.1
TABLE 1 (in accordance with EN standard 60204–1)
Values given for :
Cable with copper conductors.
Cable with PVC insulation (for other insulants see TABLE 3).
Ambient temperature 40°C max. (for others see TABLE 2)
Three-phase cable under load without including starting currents.
BT / C / E cable layout.
MAXIMUM ADMISSIBLE CURRENT
Cable section
3 x 1.5 mm²
3 x 2.5 mm²
3 X 4 mm²
3 x 6 mm²
3 x 10 mm²
3 x 16 mm²
3 x 25 mm²
3x 35 mm²
3 x 50 mm²
3 x 70 mm²
4.5.2
TABLE 2 correction factors for different ambient temperatures :
Installation manual
Seated in Cable Duct
or Cable Trough
B2
12.2 A
16.5 A
23 A
29 A
40 A
53 A
67 A
83 A
-
-
Ambient temperature
30 ° C (86° F)
35 ° C (95° F)
40 ° C (104° F)
45 ° C (113° F)
50 ° C (122° F)
55 ° C (131° F)
60 ° C (140° F)
Important
Wall Fixing
C
15.2 A
21 A
28 A
36 A
50 A
66 A
84 A
104 A
123 A
155 A
Cable Tray
E
16.1 A
22 A
30 A
37 A
52 A
70 A
88 A
114 A
123 A
155 A
Correction factor
1.15
1.08
1
0.91
0.82
0.71
0.58