T muting (4 signals/4 sensors; time or sequence monitoring)

ESPE
S4
S3
S2
S1
d1
D
Figure 46: Connection of 4 sensors on MUTING1-4 inputs in case of 4 signal/4 sensors muting
T (bidirectional) muting timings with time monitoring
The activation of the Muting function occurs as a result of the interruption of the sen-
sors S1 and S2 (the order is not relevant) within a time of T
material moving in the opposite direction. When the delay time of T
muting function immediately stops.
NOTE: Muting operations is ceased as soon as the signal from S3 (S2 in the
opposite direction) goes inactive. An optional additional muting time Tdelay
may be set.
WARNING: If T
cuit between MUTING1 and MUTING2 input. USE ONLY if risk assessment
allows or if additional diagnostic measure are implemented (eg. Mute
Enable signal configured). ????????
S1
S2
S3
S4
MUTING STATE
0s ≤ T
< T
12
Figure 47: 4 signals T Muting Timings (time monitoring)
24Vdc
S2
L
V
24Vdc
S4
Min is set to 0 the light curtain cannot detect a short cir-
12
both directions
max
0s ≤ T
< T
max
12
12
12
t < muting timeout
24Vdc
MUTING1
S1
MUTING2
24Vdc
MUTING3
S3
MUTING4
max or S4 and S3 with
12
max is exceeded
12
ACTIVE
INACTIVE
ACTIVE
INACTIVE
ACTIVE
INACTIVE
ACTIVE
INACTIVE
ON
OFF
T Delay
PRODUCT REFERENCE GUIDE
MUTING
ESPE
71