Communication Specifications - CKD IO-Link FCM Series Manual

Io-link compatible compact flow rate controller
Table of Contents

Advertisement

RAPIFLOW
Applicable fluids/flow rate control range
Model No.
FCM-9500 AI
FCM-0001 AI
FCM-0002 AI
FCM-0005 AI
FCM-0010 AI
FCM-0020 AI
FCM-0050 AI
FCM-0100 AI
(Resin type only)
FCM-9500 AR
FCM-0001 AR
FCM-0002 AR
FCM-0005 AR
FCM-0010 AR
FCM-0020 AR
FCM-0050 AR
FCM-9500 O2/LN/C1/C3
FCM-0001 O2/LN/C1/C3
FCM-0002 O2/LN/C1/C3
FCM-0005 O2/LN/C1/C3
FCM-0010 O2/LN/C1/C3
FCM-0002 H2/HE
FCM-0005 H2/HE
FCM-0010 H2/HE
FCM-0020 H2/HE

Communication specifications

Descriptions
Communication protocol
Communication protocol version
Transmission bit rate
Port type
Process data length (input)
®
FCM Series Variation
Flow rate control range (L/min)
Applicable
fluids
0.01
0.1
AIR
Air
N
2
Nitrogen
Ar
Argon
O
2
Oxygen
13A
City gas
CH
4
Methane
C
H
3
8
Propane
H
2
Hydrogen
He
Helium
Details
IO-Link
V1.1
COM3 (230.4 kbps)
A
10 byte
1
10
100
0.015 to 0.5
0.03 to 1
0.06 to 2
0.15 to 5
0.3 to 10
0.6 to 20
1.5 to 50
3 to 100
0.015 to 0.5
0.03 to 1
0.06 to 2
0.15 to 5
0.3 to 10
0.6 to 20
1.5 to 50
0.015 to 0.5
0.03 to 1
0.06 to 2
0.15 to 5
0.3 to 10
0.06 to 2
0.15 to 5
0.3 to 10
0.6 to 20
Descriptions
Process data length (output)
Min. cycle time
Data storage
SIO mode support
Body material
Port size
Resin
Resin
ø6 push-in
ø8 push-in
SUS
SUS
Rc1/4
9/16-18 UNF
SUS
Rc1/4
9/16-18 UNF
SUS
Rc1/4
9/16-18 UNF
Rc1/4
SUS
9/16-18 UNF
1/4" double
barbed fitting
1/4" JXR
male fitting
Details
4 byte
2 ms
1k byte
No

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IO-Link FCM Series and is the answer not in the manual?

Table of Contents