Abb. 4 Rj45 Socket Front View; Tab. 13 Pin Assignment Rj45 Ethercat; Tab. 14 Function Of The Leds - KEB COMBIVERT F6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

Connection
8
1
Abb. 4: RJ45 socket front view
Light pattern NET ST LED (red/
green combination)
ma_dr_f6-cu-p-inst-20182705_en
Max. number PDOUT data
Max. number PDIN data
Acyclic data traffic:
Distributed Clocks (DC)
Minimum FSoE watchdog time
PIN
1
2
3
4
5
6
7
8
Tab. 13: PIN assignment RJ45 EtherCAT
LED / light pattern
Yellow
Green
Off
On
Flicker
Tab. 14: Function of the LEDs
According to ETG1300, the NET ST LED is a combination of RUN and ERROR
LED.
Status
Light pattern
init
0
Pre-Op
g-0 (grid 50 ms)
Safe-Op
g-0-0-0-0-0 (grid 200 ms)
Op
g (permanent)
error
R (permanent)
LOAD ERROR
r-0 (grid 50 ms)
Fieldbus interfaces | 7
Max. 2 PDOs; Mapping freely selectable.
32 Byte + optional FSoE data.
64 Byte + optional FSoE data (from SW
2.8).
Max. 2 PDOs; Mapping freely selectable.
32 Byte + optional FSoE data.
64 Byte + optional FSoE data (from SW
2.8).
Supported mailbox protocols CoE; SDO
download; SDO upload (Complete Ac-
cess is not supported); Emergency
Yes, 32 Bit; minimum cycle time:
500 µs (is22=8 x tp)
250 µs (is22=4 x tp) from SW 2.8
=> Synchronous communication mode
35  ms (safety module type 5)
RJ45 without supply voltage
(Viewing with Auto-Cross Over)
TX+
TX-
RX+
Reserved
Reserved
RX-
GND
GND
Function
without function
Link/Activity
Port closed
Port open; no data traffic
Port open; with data traffic
Description
Device in INITIALISATION
status; no error
Device in PRE-OPERATIONAL
status
Device in SAFE-OPERA-
TIONAL status
Device in OPERATIONAL
status; no error
Communication or device error.
Loading error during initialisa-
tion
RX+
RX-
TX+
TX-
31