table 7-7 "Q(P)" Mode Parameters Explanation
Parameter
Q(P) Curve
QP_P1
QP_P2
QP_P3
QP_K1
QP_K2
QP_K3
QP_
EnterVoltage
QP_
ExitVoltage
QP_
ExitPower
QP_
EnableMode
* Curve C is reserved and consistent with Curve A currently.
"Q(U)" Mode
80
Explanation
Select corresponding curve according to local
regulations
Output power at point P1 on the Q(P) mode curve
(in %)
Output power at point P2 on the Q(P) mode curve
(in %)
Output power at point P3 on the Q(P) mode curve
(in %)
Power factor at point P1 on the Q(P) mode curve
Power factor at point P2 on the Q(P) mode curve
Power factor at point P3 on the Q(P) mode curve
Voltage for Q(P) function activation (in %)
Voltage for Q(P) function deactivation (in %)
Power for Q(P) function deactivation (in %)
Unconditional activation/deactivation of Q(P)
function
figure 7-18 Reactive Power Regulation Curve in Q(P) Mode
User Manual
Range
A, B, C
*
0.0 %–100.0 %
20.0 %–100.0 %
20.0 %–100.0 %
Curve A/C: 0.800
to 1.000
Curve B: -0.600
to 0.600
100.0 %–110.0
%
90.0 %–100.0 %
1.0 %–100.0 %
Yes, No