Settings - Siemens SIPROTEC 7SJ61 Manual

Multi-functional protective relay with bay controller
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

Functions
2.13 Flexible Protection Functions
2.13.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
DROPOUT RATIO
0A
DROPOUT RATIO
198
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
Please select
Current
Binary Input
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Exceeding
Dropping below
Ia
Ib
Ic
In
In sensitive
In2
Pickup Threshold
Pickup Threshold
0.001 .. 1.500 A
15 .. 100 %
0.00 .. 3600.00 sec
0.00 .. 60.00 sec
0.00 .. 60.00 sec
0.70 .. 0.99
1.01 .. 3.00
Default Setting
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Ia
Current
0.100 A
Pickup Threshold
20 %
Pickup Threshold
1.00 sec
Trip Time Delay
0.00 sec
Pickup Time Delay
0.00 sec
Dropout Time Delay
0.95
Dropout Ratio
1.05
Dropout Ratio
C53000-G1140-C210-1, Release date 02.2008
Comments
SIPROTEC, 7SJ61, Manual

Advertisement

Table of Contents
loading

Table of Contents