Functions
2.6 Motor Protection
2.6.4
Motorprotection (Motor Starting Protection 48, Motor Restart Inhibit 66,
LoadJam)

2.6.4.1 Settings

The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
4101
FCT 48/66
4102
STARTUP CURRENT
4103
STARTUP TIME
4104
LOCK ROTOR TIME
4105
STARTUP T WARM
4106
TEMP.COLD MOTOR
4301
FCT 66
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL
4306
MAX.WARM STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
4311
ROTOR OVERLOAD
4401
Load Jam Prot.
122
C
Setting Options
OFF
ON
1A
0.50 .. 16.00 A
5A
2.50 .. 80.00 A
1.0 .. 180.0 sec
0.5 .. 180.0 sec; ∞
0.5 .. 180.0 sec; ∞
0 .. 80 %; ∞
OFF
ON
1.10 .. 10.00
1 .. 320 sec
0.0 .. 320.0 min
1A
0.20 .. 1.20 A
5A
1.00 .. 6.00 A
1 .. 4
1 .. 2
0.2 .. 100.0
0.2 .. 100.0
0.2 .. 120.0 min
ON
OFF
Alarm Only
OFF
ON
Alarm Only
Default Setting
OFF
48 / 66 Motor (Startup
Monitor/Counter)
5.00 A
Startup Current
25.00 A
10.0 sec
Startup Time
2.0 sec
Permissible Locked Rotor
Time
10.0 sec
Startup Time for warm
motor
25 %
Temperature limit for cold
motor
OFF
66 Startup Counter for
Motors
4.90
I Start / I Motor nominal
10 sec
Maximum Permissible
Starting Time
1.0 min
Temperature Equalizaton
Time
1.00 A
Rated Motor Current
5.00 A
2
Maximum Number of
Warm Starts
1
Number of Cold Starts -
Warm Starts
5.0
Extension of Time Con-
stant at Stop
2.0
Extension of Time Con-
stant at Running
6.0 min
Minimum Restart Inhibit
Time
ON
Rotor Overload Protection
OFF
Load Jam Protection
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008