Mounting and Commissioning
3.1 Mounting and Connections
Input/Output Board A–I/O-2 for 7SJ61.../FF
The layout of the printed circuit board for the input/output board A–I/O-2 is illustrated in the following figure. The
set nominal currents of the current input transformers and the selected operating voltage of binary inputs BI4
to BI11 are checked.
Figure 3-8
The jumpers X60 to X63 must all be set to the same rated current, i.e. one jumper (X61 to X63) for each input
transformer and in addition the common jumper X60. The jumper X64 determines the rated current for the input
I
and may thus have a setting that deviates from that of the phase currents. In models with sensitive ground
N
fault current input there is no jumper X64.
Jumpers X80 to X85 are irrelevant for 7SJ61 devices.
Jumpers X21 to X28 do not exist in device versions 7SJ610*-.
274
Input/output module A–I/O-2 for devices (releases .../FF and higher) with representation of the
jumper settings required for the board configuration
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008