Technical Data
4.13 Ground Fault Protection 50N(s), 51N(s)
Logarithmic Inverse Trip Time Characteristics
Figure 4-11
Logarithmic inverse
Note: For I/51Ns PICKUP > 35 the time applies for I/51Ns PICKUP = 35
348
Trip time characteristics of inverse time ground fault protection with logarithmic inverse char-
acteristic
t = 51Ns MAX. TIME DIAL - 51Ns TIME DIAL·ln(I/51Ns PICKUP)
SIPROTEC, 7SJ61, Manual