2.8.1.6 Settings

The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
8101
MEASURE. SUPERV
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
Σ I THRESHOLD
8106
Σ I FACTOR
8107
FAST Σ i MONIT
8109

2.8.1.7 Information List

No.
Information
161
Fail I Superv.
Failure Σ I
162
163
Fail I balance
175
Fail Ph. Seq. I
197
MeasSup OFF
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
C
Setting Options
OFF
ON
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
0.10 .. 0.90
0.05 .. 2.00 A; ∞
1A
0.25 .. 10.00 A; ∞
5A
0.00 .. 0.95
OFF
ON
Type of In-
formation
OUT
Failure: General Current Supervision
OUT
Failure: Current Summation
OUT
Failure: Current Balance
OUT
Failure: Phase Sequence Current
OUT
Measurement Supervision is switched OFF
Default Setting
ON
Measurement Supervision
0.50 A
Current Threshold for
Balance Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.10 A
Summated Current Moni-
toring Threshold
0.50 A
0.10
Summated Current Moni-
toring Factor
ON
Fast Summated Current
Monitoring
Comments
Functions
2.8 Monitoring Functions
Comments