Addr.
Parameter
3301
INTERM.EF
3302
Iie>
3302
Iie>
3302
Iie>
3303
T-det.ext.
3304
T-sum det.
3305
T-reset
3306
Nos.det.
4001
FCT 46
4002
46-1 PICKUP
4003
46-1 DELAY
4004
46-2 PICKUP
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A
46 T DROP-OUT
4101
FCT 48/66
4102
STARTUP CURRENT
4103
STARTUP TIME
4104
LOCK ROTOR TIME
4105
STARTUP T WARM
4106
TEMP.COLD MOTOR
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
49 Θ ALARM
4204
4205
I ALARM
4207A
Kτ-FACTOR
4208A
T EMERGENCY
4209
49 TEMP. RISE I
4210
49 TEMP. RISE I
4301
FCT 66
4302
IStart/IMOTnom
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
Function
C
Intermit. EF
OFF
ON
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
0.005 .. 1.500 A
Intermit. EF
0.00 .. 10.00 sec
Intermit. EF
0.00 .. 100.00 sec
Intermit. EF
1 .. 600 sec
Intermit. EF
2 .. 10
46 Negative Seq
OFF
ON
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
Normal Inverse
Very Inverse
Extremely Inv.
46 Negative Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
46 Negative Seq
1A
0.10 .. 2.00 A
5A
0.50 .. 10.00 A
0.50 .. 15.00 ; ∞
46 Negative Seq
0.05 .. 3.20 sec; ∞
46 Negative Seq
46 Negative Seq
Instantaneous
Disk Emulation
46 Negative Seq
0.00 .. 60.00 sec
48/66 Motorprot
OFF
ON
48/66 Motorprot
1A
0.50 .. 16.00 A
5A
2.50 .. 80.00 A
48/66 Motorprot
1.0 .. 180.0 sec
0.5 .. 180.0 sec; ∞
48/66 Motorprot
0.5 .. 180.0 sec; ∞
48/66 Motorprot
0 .. 80 %; ∞
48/66 Motorprot
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
1.0 .. 10.0
49 Th.Overload
10 .. 15000 sec
49 Th.Overload
40 .. 200 °C
49 Th.Overload
104 .. 392 °F
48/66 Motorprot
OFF
ON
48/66 Motorprot
1.10 .. 10.00
Setting Options
Default Setting
OFF
1.00 A
5.00 A
1.00 A
5.00 A
1.000 A
0.10 sec
20.00 sec
300 sec
3
OFF
0.10 A
0.50 A
1.50 sec
0.50 A
2.50 A
1.50 sec
Extremely Inv.
Extremely Inv.
0.90 A
4.50 A
5.00
0.50 sec
Instantaneous
0.00 sec
OFF
5.00 A
25.00 A
10.0 sec
2.0 sec
10.0 sec
25 %
OFF
1.10
100.0 min
90 %
1.00 A
5.00 A
1.0
100 sec
100 °C
212 °F
OFF
4.90
Appendix
A.8 Settings
Comments
Intermittent earth fault protection
Pick-up value of interm. E/F
stage
Pick-up value of interm. E/F
stage
Pick-up value of interm. E/F
stage
Detection extension time
Sum of detection times
Reset time
No. of det. for start of int. E/F prot
46 Negative Sequence Protec-
tion
46-1 Pickup
46-1 Time Delay
46-2 Pickup
46-2 Time Delay
46 IEC Curve
46 ANSI Curve
46-TOC Pickup
46-TOC Time Dial
46-TOC Time Dial
46-TOC Drop Out
46 Drop-Out Time Delay
48 / 66 Motor (Startup Moni-
tor/Counter)
Startup Current
Startup Time
Permissible Locked Rotor Time
Startup Time for warm motor
Temperature limit for cold motor
49 Thermal overload protection
49 K-Factor
Time Constant
49 Thermal Alarm Stage
Current Overload Alarm Setpoint
Kt-FACTOR when motor stops
Emergency time
49 Temperature rise at rated sec.
curr.
49 Temperature rise at rated sec.
curr.
66 Startup Counter for Motors
I Start / I Motor nominal
407