124
PCS100 UPS-I User Manual

13.2 Control Connections

The PCS100 UPS-I includes control connections for the need of local control or monitoring of the system.
Control connection terminals are located on Auxiliary Master Module at the bottom of the Master Inverter
Enclosure.
13.2.1

Digital Inputs and Outputs

Digital input and output terminals are located on Auxiliary Master Module at the bottom of the Master Inverter
Enclosure and numbered as shown in Figure 13-1 and explained in Error! Reference source not found..
Terminal
Description
Number
1
Relay output / 250 Vac/30 Vdc, 1 A / NC
2
Relay output / 250 Vac/30 Vdc, 1 A / C
3
Relay output / 250 Vac/30 Vdc, 1 A / NO
4
Relay output / 250 Vac/30 Vdc, 1 A / NC
5
Relay output / 250 Vac/30 Vdc, 1 A / C
6
Relay output / 250 Vac/30 Vdc, 1 A / NO
7
Relay output / 250 Vac/30 Vdc, 1 A / NC
8
Relay output / 250 Vac/30 Vdc, 1 A / C
9
Relay output / 250 Vac/30 Vdc, 1 A / NO
10
Isolated thermal switch / 24 Vac/24 Vdc, 1
A / NC
11
Isolated thermal switch / 24 Vac/24 Vdc, 1
A / NC
12
Dry contact only; return wire
13
Dry contact only; start on closing edge.
14
Dry contact only; return wire
RUN
1
NC
250 Vac / 30
2
C
Vdc
3
NO
1 A
WARNING
4
NC
250 Vac / 30
5
C
Vdc
6
NO
1 A
FAULT
7
NC
250 Vac / 30
8
C
Vdc
9
NO
1 A
10
NC
TX ALARM
24 Vac/Vdc, 1 A
11
NC
12
0 V
13
START
14
0 V
15
STOP / RESET / INHIBIT
16
LOOP
Figure 13-1: Remote Control and Monitoring Terminals
PCS100 UPS-I
1
2
3
4
5
6
7
8
9
10
200º
11
C
12
13
-
14
+
15
Inhibit switch;
16
Located inside
inverter cabinet
door
(fitted at factory)
Name
RUN
RUN
RUN
WARNING
WARNING
WARNING
FAULT
FAULT
FAULT
Not used on PCS100 UPS-I.
Not used on PCS100 UPS-I.
Remote start input – return
Remote start Input – only used if a remote Start
is required
Remote Stop/Reset – return