15.4 Clearances

The following clearances are required for all
enclosures:
Allow 200 mm (minimum) above
Allow 1500 mm (recommended) clearance
in front
Allow 400 mm (recommended) clearance
at the rear for testing fans, access to
interconnecting wiring and installation of
bus bars. 200 mm at the rear is the
minimum
clearance
ventilation of enclosures placed side-by-
side and 400 mm if placed back-to-back.
(Exception: The Coupling Transformer
and Utility Disconnect can be placed
back-to-back without any clearance.)
No side clearance required
Side clearance to the wall at the side
where the cabinet outmost hinges of
minimum 400 mm is recommended to
allow the doors to open sufficiently. The
doors must open 120° to allow normal
cabinet to access the PCS100 UPS-I
module replacement.

15.5 Layout Plans

For layout plans and dimension information refer to the PCS100 UPS-I Technical Catalogue, Document number
2UCD120000E002, and installation documents / drawings.