15.4 Clearances
The following clearances are required for all
enclosures:
Allow 200 mm (minimum) above
–
Allow 1500 mm (recommended) clearance
–
in front
Allow 400 mm (recommended) clearance
–
at the rear for testing fans, access to
interconnecting wiring and installation of
bus bars. 200 mm at the rear is the
minimum
clearance
ventilation of enclosures placed side-by-
side and 400 mm if placed back-to-back.
(Exception: The Coupling Transformer
and Utility Disconnect can be placed
back-to-back without any clearance.)
No side clearance required
–
Side clearance to the wall at the side
–
where the cabinet outmost hinges of
minimum 400 mm is recommended to
allow the doors to open sufficiently. The
doors must open 120° to allow normal
cabinet to access the PCS100 UPS-I
module replacement.
15.5 Layout Plans
For layout plans and dimension information refer to the PCS100 UPS-I Technical Catalogue, Document number
2UCD120000E002, and installation documents / drawings.
required
for