ABB PCS100 UPS-I User Manual page 121

Industrial uninterruptable power supply
Table of Contents

Advertisement

PCS100 UPS-I User Manual
Address Name
17
Inverter DC Bus
Voltage minimum
18
Inverter DC Bus
Voltage maximum
19
Storage DC Voltage
(Same as on Status
page)
20
Active Event Code
(Same as GDM
status line)
21
Discharge Count
22
Detailed Status
23
Read Test
100 &101 Date and Time
(To read & set the
date and time)
102
Read/Write Test
Address Name
1001-
Cached registers 1-
1023
23 (see section
Error! Reference
source not found.)
Access
Type
Read Only 16-bit,
Signed
Read Only 16-bit,
Signed
Read Only 1- bit,
Signed
Read Only 16-bit,
Signed
Read Only 16-bit,
Signed
Read Only 16-bit,
Signed
Read Only 16 bit
unsigned
Read/Writ
32bit
e
Unsigned
Read/Writ
16 bits
e
Table 12-2: PCS100 UPS-I Modbus TCP user parameters
Access
Type
Read Only As for
registers
1-23
Table 12-3: PCS100 UPS-I Modbus TCP cached user parameters
Raw Value & Scaling
Voltage (Volts) = 480 * 0.816496 * Raw value / 8192
(Inverter module with min DC voltage)
Voltage (Volts) = 480 * 0.816496 * Raw value / 8192
(Inverter module with max DC voltage)
Voltage (volts) = 480 * 0.816496 * Raw value / 8192
Refer to Table 11-2 for a list of event codes. Code 0
indicates there are no active events (no
warning/fault)
Discharge count = Raw value
0 – System is initializing (Startup web page)
1 – Fault
2 - Clearing Fault
3 - Static Bypass
4 - Starting
5 - On Line
20 – Inverter Not ready (Starting - System Bypass
state shown in the Figure 7-6 (state flow diagram))
21 – Discharging
22 – Discharging (Wait for stable mains)
23 – Discharging (Synchronizing)
24 – Online
25 – Mains Lost while returning to mains.
26 – Discharge T/O
27 – Storage Empty
28 – Inverter Off (problem with inverter. FSB
closed)
29 – Discharge Overload
30 – Test_Mode (UD Open test (menu 612) - refer to
Figure 7-6)
31 –Walking in (28 Transfer Back - refer to Figure
7-6)
Counts up by one for each access to this register.
Can be used by Modbus masters to check
connection.
Unit is seconds.
Datum is 00:00:00 1/1/1970.
e.g.: 1297296764 is 00:12:31 10/2/2011
Register for use by customer for testing Modbus.
Not used by PCS100 UPS-I
Raw Value & Scaling
Same as for registers 1-23
121