PCS100 UPS-I User Manual
10.3.10

Menu 900 Commissioning

Menu 900 Commissioning
This menu contains parameters only used during commissioning or advanced setup.
Parameter:
905 GDM Remote Menus
Function:
Enables remote access to the GDM menus via the GDM Ethernet connection
Access:
Tech
Note:
If enabled, allows an operator to remotely configure the PCS100 UPS-I.
Parameter:
915 Relay Test Mode
Function:
Turns relays on and off
Range:
7 test options
Factory
Off
Setting:
Access:
Tech
Parameter:
916 RMS Line Gnd Test
Function:
Changes status page voltage readings from L-L to L-G
Range:
True / False
Factory
False
Setting:
Access:
Tech
Note:
Used for calibration of voltage sensors
Parameter:
919 Disconnect
Function:
Selects any of the various test modes for the Utility Disconnect
Range:
Normal: SCR Conducting.
SCR Open MAY DROP LOAD
Factory
Normal.
Setting:
Access:
Tech.
CAUTION
The load may be dropped if this parameter is set incorrectly
Parameter:
920 CESE
Function:
Selects the CESE version
Range:
Unknown, CESE Mk1, CESE Mk2
Factory
Set to match the CESE hardware version
Setting:
Access:
Tech
Note:
If fault code 42 "Initialisation Failure" occurs while the inverters are displaying L0 check
the SCM status (refer to document 2UCD200000E430). Cycle power. Ensure that the CESE
version is set to match the hardware version installed.
Table 10-11: Menu 900 Commissioning