Technical Specification; Utility - Input - ABB PCS100 UPS-I User Manual

Industrial uninterruptable power supply
Table of Contents

Advertisement

PCS100 UPS-I User Manual

4 TECHNICAL SPECIFICATION

NOTE: These specifications apply to the standard PCS100 UPS-I range and may be superseded by special
variations stated on the PCS100 UPS-I rating label or User Manual Addendum.
4.1 Utility – Input
Rated Supply Voltage
(Operating range)
Voltage tolerance
Nominal supply frequency
Frequency tolerance
Maximum Continuous
Voltage
Power system
Harmonics
Overvoltage category
Fault capacity
Efficiency (400 V & 480 V
models)
Efficiency (220 V models)
Overload and Short Circuit
Protection
Overload Capacity
220 V (208 – 220 V)
400 V (380 – 400 V)
480 V (415 - 480 V)
Note: Operation at lower than the rated voltage results
in less kVA per module. Consult the rating tables for
more information.
± 10%
50 Hz or 60 Hz
± 5 Hz
110%
3-phase + Neutral (4-Wire) Centre ground referenced
(TN-S)
For use in other power systems refer to ABB Document
2UCD120000E017
IEC 61000-2-4 Class 2 (Utility THDv < 8%)
Note: For THDv > 8%, please refer to factory.
For applications where THDv is above 10% lifetime of
components may be significantly affected, please refer
to factory.
III
Refer to the model tables in this catalogue
99% (typical)
98% (typical)
Circuit Breaker (not included)
120% for 60 s
150% for 30 s
200% for 10 s
300% for 5 s
Not more than once every 10 minutes. For more
information refer the Input Circuit Protection
description in this catalogue