24
PCS100 UPS-I User Manual
Nominal ratings
Rated power (kVA)
Inverter Rated Current
Utility Disconnect Rated Current
Overload ratings
Inverter
Utility Disconnect
Rated power (kVA) at rated voltage and power factor.
Rated inverter current available during PCS100 UPS-I
discharge mode
Rated UD current during PCS100 UPS-I online mode
110% of rated current for 30 s
120% of rated current for 60 s every 10 minutes
150% of rated current for 30 s every 10 minutes
200% of rated current for 10 s every 10 minutes
300% of rated current for 5 s every 10 minutes
Table 3-3: PCS100 UPS-I model range table definition explanations