PCS100 UPS-I User Manual
12.2.5

Service Page

The Service Page has following three functions.
12.2.5.1

Download Service Information.

Information useful for the ABB service department such as parameter settings and the event log can be
downloaded. The information is contained within a zip file which can be sent to the ABB factory to assist in
analyzing problems with the product. To download this information:
a.
Click Service Information Download. You will be informed that a service file is being created. Creating a
service file is a five-step process. This may take some time, e.g., five minutes. You will then be informed
that the service information is ready to download.
b. When prompted by your browser, save the file to the relevant location on your device.
12.2.5.2

Update the Product Firmware

Click Firmware Upload, then click Browse and select the software file provided by the ABB factory. The name of
the software file typically starts with a 4 digit number beginning with 7. Once the file has down loaded the system
must be rebooted via parameter 051 System Reboot.
For further information on upgrading software over Ethernet see document 2UCD200000E002_a How to
Upgrade System Software over Ethernet.
12.2.5.3

Make a change to an internal parameter

Enter the factory supplied code to change the required internal parameter. When a correct code is entered the
message "Parameter Write Result = OK" will be displayed. If an incorrect code is entered the message "Sorry, value
entered is not correct" is displayed. This function is the same as parameter 53 Set Parameter.
Table 12-1: Remote Web Pages Service Page