Status Bar - ABB PCS100 UPS-I User Manual

Industrial uninterruptable power supply
Table of Contents

Advertisement

54
PCS100 UPS-I User Manual
7.1.3

Status Bar

The status bar displays the PCS100 UPS-I status and any warning or fault code (if present).
PCS100 UPS-I
Status
1.
PCS100 UPS-I Status. Refer to Table 7-4 for a complete list of status messages. See also Figure 7-6
2.
Fault or Warning description. The event code number can be found in the event log. Refer to section 11 for
complete event descriptions.
3.
"Warning" will be displayed if any warning condition exists.
Note:
The Status Bar will only display the most recent event or what is considered the most important event. Touch the
Status Bar and a list of all faults and warnings presently active will be displayed.
Color of status bar depends on PCS100 UPS-I status as shown in Table 7-3.
Status Bar Color
Green
Green with yellow flashing warning cell
White
White with yellow flashing warning cell
Red and White flashing
Yellow
Figure 7-6 shows the PCS100 UPS-I state flow diagram.
PCS100 UPS-I Status
Static bypass
Booting or system down
Fault
Starting – system bypassed
On line
Inverter not ready
Discharge t/o
Figure 7-5: PCS100 UPS-I Status Bar example
PCS100 UPS-I Status
Run (Online, Discharging, etc.) with no warning
Run (Online, Discharging, etc.) with Warning present
Static Bypass
Static Bypass with Warning present
Fault
Starting – System Bypassed
Table 7-3: PCS100 UPS-I Status Bar Colors
Description
The PCS100 UPS-I is stopped: The Fail-Safe Bypass is closed. (See
Figure 7-4)
The PCS100 UPS-I is booting up or initializing or there is no
response from the master this could be due to the GDM CAN
cable disconnected.
The PCS100 UPS-I has tripped, or it is clearing a trip.
Waiting until the inverters start. The storage DC voltage must be
greater than 650VDC, PLL locked, FSB open and the utility voltage
within thresholds (parameters 530,531,533 and 535) for the UPS-I
to go Online.
Load is operating from the utility supply. The utility voltage and
frequency are within limits. The PCS100 UPS-I is ready to back up
the load in case the utility voltage or frequency goes beyond the
thresholds
Inverter Not Ready
The PCS100 UPS-I has returned to the utility supply. The PCS100
Warning Condition
Fault or Warning
description