4.7 Energy Storage - Batteries

System DC Nominal Voltage
Discharging Voltage Range
Overload Capacity
Rated Power
Autonomy Period
Operating Temperature
Design Life
Cycle Life
Recharge Time

4.8 Event Recording

Measurement Method
Sample Time
Resolution of time stamp in
event log
Measurement Type

4.9 Environmental

Operating temperature range
Operating altitude
Capacity derating with
altitude
Humidity
Pollution degree rating
Noise
Storage temperature range
Packaging
672V DC (56 x 12V DC)
780 V DC to 554 V DC
100%
240 kW per string
30 s @ 240 kW
For more information refer to ABB Document
2UCD120000E018
15 °C to 25 °C (recommended)
10 years at 25 °C
> 800 (full load 30 s discharge)
< 30 min
Line to Line
125 µs
10 ms
Half-cycle RMS according to IEC 61000-4-30
0° C to 40° C (32° F to 104° F)
< 1000 m without derating
1% every 100 m
above 1000 m
2000 m maximum
< 95%, non-condensing
2
< 75dBA @ 2 m
-30° C to 50° C (-22° F to 122° F)
Must be kept dry at all times including
transportation and storage. Protect against contact
with rain or other water or liquids and do not store
in damp or humid conditions.