Fig. 40: Menu 5.42
Fig. 41: Menu 5.43
Fig. 42: Menu 5.44
Fig. 43: Menu 5.50
Fig. 44: Menu 5.51
Fig. 45: Menu 5.57
36
Menu no.
5.42
Software version: All
Description
"Pump kick interval"
Value range
1 ... 336 h
Factory setting
24 h
Explanation
Time after which a pump kick takes place.
Menu no.
5.43
Software version: All
Description
"Pump kick duration"
Value range
0 ... 60 s
Factory setting
5 s
Explanation
How long a pump kick runs for a pump.
Menu no.
5.44
Software version: All
Description
Activation delay after power failure
Value range
0 ... 180 s
Factory setting
3 s
Explanation
Time until the switchgear automatically restarts after a power
outage.
Menu no.
5.50
Software version: All
Description
Dry-running level (drain)/ min. water level (fill)
Value range
0 ... 12.5 m
Factory setting
0.15 m
Explanation
Enter fill level.
If the level is monitored with a separate float switch, deactiv-
ate the level sensor: Enter the value "0.00 m".
Menu no.
5.51
Software version: All
Description
High water level
Value range
0 ... 12.5 m
Factory setting
0.46 m
Explanation
Enter fill level.
Menu no.
5.57
Software version: All
Description
Max. running time per pump
Value range
0 ... 60 min
Factory setting
0 min
Explanation
Maximum permissible running time of a pump. Once the time
has been exceeded, the system switches to the next pump.
After three change cycles, the collective fault signal (SSM) is
activated.
The setting "0 min" switches the running time monitoring off.
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09