heat-timer ETS Installation And Operation Manual page 46

Electronic tempering station
Table of Contents

Advertisement

46          ETS Installation and Operation Manual
Symptom
No display or distorted 
display.
Display shows sensor 
"Open".
Display shows sensor 
"Short".
System reads incorrect 
temperature.
No hot water.
059326‐00  Rev D
Troubleshooting
Possible Cause
No power to the ETV Platinum 
Plus Control Module, incorrect 
or defective wiring.
Sensor disconnected.
Defective sensor, wires, or ETV 
Platinum Plus Control Module.
Defective sensor, wires, or ETV 
Platinum Plus Control Module.
Defective sensor or ETV 
Platinum Plus Control Module.
If a flow switch is installed, the 
Flow Switch option is set to 
"Yes", and the flow input is 
open, the mixing valve may be 
marginally closed.
Water heater malfunction.
Recommended Action(s)
Verify the ETV Platinum Plus Control Module is 
receiving power, all power wiring is in good 
condition and connected.
The ETV Platinum Plus Control Module requires 
120Vac power to terminal 1 and 2, and earth 
ground wiring to terminal 3.
Turn power to the ETV Platinum Plus Control 
Module off then back on.
Verify the sensor is properly connected to the ETV 
Platinum Plus Control Module.
Short the sensor input wires. The display should 
read "Short".
• If the display still reads "Open", the device is
defective. Replace the ETV Platinum Plus
Control Module.
• If the display reads "Short", test the sensor
wiring for continuity. Replace the sensor/
wiring.
Remove the sensor wires from the input terminals. 
The display should read "Open".
• If the display still reads "Short", the device is
defective. Replace the ETV Platinum Plus
Control Module.
• If the display reads "Open", test the sensor
wiring for continuity. Replace the sensor/
wiring.
Disconnect the wires from the input terminals. The 
display should read "Open".
• If the display does not read "Open", the device
is defective. Replace the ETV Platinum Plus
Control Module.
• If the control reads "Open", and the difference
is within 5°F, replace the sensor.
Verify Flow Switch setting and the position of the 
mixing valve.
Check water heater(s) to ensure proper operation.
Heat‐Timer Corp.