22          ETS Installation and Operation Manual
ETS startup consists of the following steps:
1. Programming the ETV Platinum Plus.
2. Calibrating the Actuator.
Programming the ETV Platinum Plus
ETV Platinum Plus Control Module Output Status LEDs
The ETV Platinum Plus has three output status LEDs:
LED
Actuator Signal
Indicates the change in the mixing valve opening. Any time the ETV Platinum Plus 
changes the valve opening, the LED will turn on for approximately one second. If the LED 
remains lit, the control is sending the Actuator a "fully open" or "fully close" signal.
No Flow
Indicates no flow exists when lit.
NOTE: This indicator is only applicable when using a Flow Switch as PROVE of flow in 
applications without a building recirculation system.
TMC Lockout 
Indicates the control is in lockout mode when lit. System temperature rises above the 
(High Temperature 
Alarm Limit for the Trigger Delay period, or a sensor has been disconnected. See "Alarm 
Limit)
Messages" on page 24.
After the alarm condition has been corrected, the ETV Platinum Plus must be manually 
reset to resume normal operation.
Display and Variable‐Function Buttons
The ETV Platinum Plus display shows the system sensor 
temperature and operation messages. By default, the 
display shows the current Setpoint, Alarm Limit, or the 
Modulation Output percentage. See "Display Icons and 
Messages" on page 24 for more information.
The area above the variable‐function buttons displays the 
current function for each button. This area may not be 
displayed if button activity is stopped for 30 seconds in the 
ETV + TMC mode.