heat-timer MPCQ Platinum Installation And Operation Instructions For

heat-timer MPCQ Platinum Installation And Operation Instructions For

Steam heating and sequencing control
Table of Contents

Advertisement

Quick Links

INSTALLATION AND OPERATION INSTRUCTIONS
MPCQ Platinum
STEAM HEATING AND SEQUENCING CONTROL
RESET CONTROLS FOR MULTIPLE
BOILER STEAM HEATING SYSTEMS
C O R P O R A T I O N
MENU FUNCTIONS
SELECT
ADJUST
BACK
BOILER
DAY
PREV./NEXT
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
SAFETY
GROUND
MUST BE
CONNECTED
MADE IN U.S.A.
The MPCQ Platinum is strictly an operating control. It CANNOT be used as a limit control. All boilers
must have all safety and limit controls required by code. It is the responsibility of the installer to verify
that all the safety and limits are working properly before the MPCQ Platinum is installed.
This control must be installed by a licensed electrician.
R
enters menus or accepts changes
OD= 31
selects menu items or changes settings
Est Pres at:9.0psi
returns to previous menu
selects boiler menus or next boiler
<AB>
selects next day
HIGH
steps through output status
AUTO
HELP
BYPASS
SYSTEM
A
B
2
3
4
5
6
7
8
9
SYSTEM
A
MPCQ
Platinum
DO NOT APPLY ANY VOLTAGE
o
F
SYS= 11psi
CD
EF
GH
LOW
OFF
OFF
PREV.
NEXT
BOILER
(DEL)
(DAY)
C
D
E
10
11
12
13
14
15
16
17
B
C
D
E
F
OPERATING LIMIT OUTPUTS
ROUTE SENSOR AND AUXILIARY WIRES
WARNING
R
INPUTS
T
A1
OUT
TEMP
A2
TO SENSOR TERMINALS
A3
SHUTDOWN
A4
ALL SENSORS MUST BE
GOLD SERIES SENSORS
S
S
A5
PRESS
4-20 mA
A6
+
ADJUST
A7
NETWORK
A8
A9
PRESS TO
PROVE
SELECT
A10
T
A11
AUX
TEMP 0
A12
BACK
A13
T
AUX
TEMP 1
A14
A15
T
AUX
TEMP 2
A16
A17
A18
F
G
H
18
19
20
21
22
G
H
THROUGH THIS KNOCKOUT ONLY

Advertisement

Table of Contents
loading

Summary of Contents for heat-timer MPCQ Platinum

  • Page 1 MADE IN U.S.A. WARNING The MPCQ Platinum is strictly an operating control. It CANNOT be used as a limit control. All boilers must have all safety and limit controls required by code. It is the responsibility of the installer to verify that all the safety and limits are working properly before the MPCQ Platinum is installed.
  • Page 2: Table Of Contents

    System Settings ....20 MPCQ Platinum BACnet Variable List ..35 Season..... . . 20 Platinum BACnet PICS Statement .
  • Page 3: Panel Layout

    MPCQ Platinum Installation and Operation Manual Panel Layout Digital display shows the system status, Depress the knob to move Target, outdoor, and system temperatures. forward through the menus and to To view and adjust settings, press the accept changes. To change a Depress the button to go back Adjust/Select button.
  • Page 4: Understanding Operation Concept

    1. The MPCQ Platinum starts activating steam stages when the outside temperature falls below the Outdoor Cutoff (factory set to 55°F for the day and 40°F for the night, but fully adjustable). The MPCQ Platinum will continue to bring on more stages, and/or hold all the stages on, until the system pressure reaches the set point.
  • Page 5: Set Point Operation Concept

    OSS is used in fast reacting application as in process applications, where maintaining a set point is critical. The OSS utilizes the Throttle setting, as a mean to calculate the number of stages the MPCQ Platinum shall have on at any point. For every Throttle Range below the set point an additional stage shall be turned on/energized.
  • Page 6: Boost And Early Shutdown

    PID or Oversize (Control Logic) • The MPCQ Platinum can use an algorithm (PID) to look at the rate of change in the System. If the System pressure changes quickly, the MPCQ Platinum will turn on or off stages quickly. If the pressure changes are slow or minor, the MPCQ Platinum will react slowly.
  • Page 7: Making Sure You Have The Right Control

    Vacation • The MPCQ Platinum RINet (Internet controls only) can be set to have a third space target for a specified period. This can be used for vacation situation in schools. It offers the user a significant fuel savings during those periods.
  • Page 8: Installation

    • Remember that the upgrade to Internet or BACnet control requires adding a communication board and replacing the CPU board. • When connecting the MPCQ Platinum to an Extension Panel, connect the RS485 to the back of the MPCQ Platinum. Use the center RS485 terminals on the motherboard.
  • Page 9: Install The Sensors

    ALERT Determining the proper location for the Outdoor Sensor is very important. The MPCQ Platinum will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun or covered with ice, its reading will be different from the actual Outdoor temperature (OD).
  • Page 10: Wiring

    SYSTEM Burner Stages Wiring • Each of the MPCQ Platinum outputs operates a single stage on a burner. The outputs are dry contacts only. They do not source any power. • Bring the boiler wires through one of the enclosure bottom knockouts.
  • Page 11: Wiring Network Sensors (Wireless And Mig)

    Any safety interlock MUST be wired back to the boilers or other equipment as required by code. ALERT The PROVE terminals must be shorted for MPCQ Platinum to provide heat. DO NOT remove the factory installed PROVE jumper unless replacing it with a Prove signal. Wiring Aux Input Terminals (Requires Internet Communication Package Upgrade) •...
  • Page 12: Wiring To An Extension Panel

    • Each Extension Panel has 8 Lockout inputs that can be used by the MPCQ Platinum when sequencing the boilers. • The first Lockout terminals on the first Extension panel will control the first MPCQ Platinum boiler, the boiler that has stage A as its first stage.
  • Page 13: Connecting To The Bacnet Ip

    MPCQ Platinum Installation and Operation Manual Connecting to the BACnet IP BACnet Communiation • The MPCQ Platinum control comes either as a Standard without any communication Connection to Back of Control or with Internet or BACnet communication. • Any MPCQ Platinum with BACnet communication control package has a BACnet BACnet or Communication Board installed on the back of the main board.
  • Page 14: Menu Settings

    Heat-Timer Corp. Menu Settings SHIFT P.30 SHIFT FROM NIGHT TO ------ SETTINGS ------ Extend Day Sched Night Shift <System Settings> Schedule <Schedules> SHIFT FROM DAY TO <Maintenance> Night <System Startup> Extend Day - EXTEND DAY TIME- Schedule 90 Min SYSTEM STARTUP P. 17 SCHEDULES P.26...
  • Page 15 MPCQ Platinum Installation and Operation Manual -------- SEASON ------- SEASON P.20 ------ SETTINGS ------ When in Winter Season Summer Winter Summer Shift <System Settings> <Schedules> ------ SET POINT ---- When in <Maintenance> Summer 10.0 psi <System Startup> SETTINGS P.20 -- DAY ADJUSTMENT --...
  • Page 16: Setting The Control

    When clicked on a specific menu item will provide help instructions. When powering up the MPCQ Platinum for the first time, it will take you through an 70 second count down followed by the System Startup Settings then another 10 second boot setup and finally end with the default system screen. Once the control is mounted and wired, set up an initial pilot program.
  • Page 17: Startup Settings

    (See page 4) or by maintaining an adjustable Set Point. • When Cycle is selected, the MPCQ Platinum will adjust the cycle on length according to the Outdoor Temperature and the Heat Adjustment. This option will provide more comfort and fuel savings for building heating applications.
  • Page 18: Boiler Type

    Default: varies SELECT Settings/System Startup/.../Total Boiler • The MPCQ Platinum can control up to a total of 24 stages using a maximum of two Extension panels. Enter the total number of boilers to be controlled. • Make sure that the extension panels are connected (See page 12) and powered before adjusting the Total Boiler value.
  • Page 19 Year, Month, Day, Time 2000 SELECT Settings/System Startup/.../Set Year • Entering the correct date and time assures that the MPCQ Platinum will follow the ----- SET MONTH ----- schedules based on the correct time. • Use the Select/Adjust button to change and accept date and time values.
  • Page 20: System Settings

    6. Wait until the radiator is warm. Depending on the steam distribution, this may take up to half an hour, or even more. 7. Return to the MPCQ Platinum control and read the current System pressure. Adjust the System Sensor Set Point down to that...
  • Page 21: Day/Night Heat Adjustment

    SELECT Settings/System Settings/Day Cutoff SELECT Settings/System Settings/Night Cutoff OUTDOOR DAY CUTOFF • The Day/Night Cutoffs will determine when can the MPCQ Platinum start heating 55 F the System. When the Outdoor temperature (OD) is above the Outdoor Cutoff, the MPCQ Platinum will turn off all burner stages. When the Outdoor temperature (OD)
  • Page 22: System Run-On

    SELECT Settings/System Settings/More Settings/Setback • When in Set Point Operating Mode, the MPCQ Platinum has two heat levels. The Day Time setting is for when a building is occupied and people are active. It follows that Day schedule. The Night Time settings hold a lower pressure set point when the building is unoccupied and it will follow the Night schedule.
  • Page 23: Stage Settings

    -- REACTION TIME ---- • After the MPCQ Platinum turns on a stage trying to meet a set point, it will not turn on another stage until the reaction time has elapsed. Then, if a stage is needed, it will be energized.
  • Page 24: Minimum Run Time

    Platinum brings on the Lead Stage, the Set Point is quickly exceeded and the MPCQ Platinum turns the Lead Stage off. • To prolong the run time during this type of condition, use the Last Stage Hold setting. The MPCQ Platinum will allow the system pressure to exceed the Set Point by the Last Stage Hold value before the Lead Stage is turned off.
  • Page 25: Lead Boiler And Rotation Settings

    • If Manual is selected, the Lead Boiler will not automatically rotate. • In Manual, whichever Boiler is presently the Lead will remain the Lead until there is a power failure. Then the MPCQ Platinum will revert to the lowest Boiler in Auto Mode.
  • Page 26: Boiler Operation Mode

    The boiler is in lockout due to lockout input is shorted on the Extension. Schedules SELECT Setting//Schedules ----- SCHEDULES ----- • The MPCQ Platinum has two levels of heat. The Day Time level is used when a Day/Night Schedule building is occupied and people are active. Copy Schedule •...
  • Page 27 Shutdown start time will vary based on Outdoor temperature and Boost Adjustment. See page 22. • In this area of the MPCQ Platinum control menu 3 buttons will take effect. The NEXT button will allow the scroll between the 4 different settings of a specific weekday.
  • Page 28: Copy Schedule

    ALERT Remember that the battery is the only backup for the Date and Time. If no power is supplied to the MPCQ Platinum and there was no battery or battery had no power, date and time values will be lost and will need to be re-entered.
  • Page 29: Maintenance

    Heat is Established. • Note the Fast Cycle feature only works when the MPCQ Platinum is in a cycle. It cannot be used to override the Heat Established function or to prevent the Pressure Lockout.
  • Page 30: Override Remote Changes

    Instead of re-programming the control to keep it from going into the Night mode, simply select the Shift to Extend Day. • The amount of time the MPCQ Platinum will hold the shift is based on the following: ◦ Shifting from Day to Night The control will stay in the Night mode until the start of the next programmed Day mode time.
  • Page 31: Auto/Bypass

    Stage mode. The display will change to read the total time the control has been in Bypass and all stage status will display BYP. • The switch must be in the AUTO position for the MPCQ Platinum to control the system and stage relays. • This switch will not be affected by any password setting.
  • Page 32: Communication

    • For the Day Target to be used, Space Lock must be enabled. • The Day Target is the space temperature the MPCQ Platinum will try to reach during the Boost period (Day #1 setting) when coming out of the Night Time setting.
  • Page 33: Vacation Schedule

    Internet connection by entering the IP, Mask, Gateway, and DNS --- INTERNET ID --- ---.---.---.--- information. All the information must be entered in an IP format. • On a power up, the MPCQ Platinum will have a delayed Internet start ( approximately Msk: ---.---.---.--- Gwy: ---.---.---.---...
  • Page 34: Internet Alarms

    Heat-Timer Corp. Internet Alarms • The MPCQ Platinum RINet has a set of pre-configured control alarms that can be activated through the Internet ICMS website by visiting the control Alarms webpage. • Each alarm can be activated by creating at least one delivery. Simply, click on the Alarm button.
  • Page 35: Bacnet Communication

    2nd row of the display when it is in screen saver mode. MPCQ Platinum BACnet Variable List The following is the BACnet variable list that can be used to communicate with the MPCQ Platinum. OBJ ID OBJECT NAME...
  • Page 36 Heat-Timer Corp. OBJ ID OBJECT NAME DESCRIPTION TYPE* RANGE READ ONLY 1800 MINRUN Min Runtime Minutes(72) 1-60 1900 through MODE00 through Boiler Mode 1=Auto,2=Standby,3=Off,4=On 1931 MODE31 2000 NBOILER Total Boilers 1 – 32/(BTYPE+1) 2100 NADJUST Night Heat 1=A, 2=B, 3=C, 4=D, 5=E, 6=F, 7=G, 8=H, 9=I,...
  • Page 37 MPCQ Platinum Installation and Operation Manual Boiler Type Variable Table BTYPE LEAD – Special value (Up to NBOILER –1) 1 – 32 → ‘A’ ‘B’ ‘C’ … ‘X’ ‘Y’ ‘Z’ ‘a’ ‘b’ ‘c’ ‘d’ ‘e’ ‘f’ 1 – 16 → ‘AB’ ‘CD’ ‘EF’ … ‘WX’ ‘YZ’ ‘ab’ ‘cd’ ‘ef’...
  • Page 38: Platinum Bacnet Pics Statement

    (973)575-4004 Vendor ID: 248 Product Description Various controls for heating or cooling applications. Includes Platinum Models MPC, MPCQ, HWR, HWRQ, Multi-Mod, SRC. (see http://www.heat-timer.com for more information) BACnet Standardized Device Profile (Annex L) Device Profile Product BACnet Application Specific Controller (B-ASC)
  • Page 39: Troubleshooting

    Display shows an Incorrect Temperature Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the MPCQ Platinum may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature sensor Table.
  • Page 40: Specifications

    ............Winter and Summer. 20 New Dutch Lane, Fairfield, NJ 07004 973-575-4004 • Fax 973-575-4052 • http://www.heat-timer.com C O R P O R A T I O N 059090-00 Rev.A...

Table of Contents