Page 1
With Optional BACnet Communication WARNING This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Heat-Timer control.
Dry-contact inputs. Outdoor Sensor Power modulating valve. System Output operates Boiler or Motorized Valve Connect to the system pump or valve. modulation output signal or 4-20mA BACnet Interface Ext. Interface Set Point. Module SMC Installation and Operation Manual...
In Slab Sensor Type mode, the slab sensor base and its conduit must be installed before the slab installation. However, in some sites where the concrete slab is old and cannot be altered, the SMC can operate based on the Outdoor Sensor using the Outdoor Sensor Type mode. This method does not provide any moisture detection and requires the purchase of the optional Outdoor Sensor (HT# 904220-00).
• Wire the power to the SMC. But do not power it. See "Wiring the Power" on page 12. • Wire the SMC outputs to the System and Slab Pumps, Motorized Valve, and Boiler. See "Output Wiring" on page 12.
Page 6
(and a heat-exchanger) or a 3-way hydronic mixing motorized valve. Select "Boiler" if the slab loop is heated directly by a modulating boiler. Select "Ext. Interface" if the SMC is connected to a Heat-Timer multi-boiler control (Multi-MOD Platinum, Mini-MOD, SQ-Elite, etc..). Then set the EMS 4 and 20mA set points to match the boiler control 4-20mA set points.
The higher the Slab ΔT, the more energy is being input to the slab. If the Slab ΔT is set larger than its design ΔT (Max ΔT), the slab itself may be damaged. The SMC provides a Maximum Slab ΔT adjustment.
The solution can be heated either directly using a condensing boiler or indirectly using a heat-exchanger. See "SMC Modulating a 3-Way Motorized Valve - Piping" on page 44 and pg 46. In this scenario set the following startup settings: ○...
INSTALLATION Enclosure Display Module MOUNTING ThE ENCLOSURE The SMC consists of three primary enclosure components. • The Enclosure Display Module: contains the control electronic board, display, buttons, LEDs, and wiring terminals. It has two screws to hold it to the base.
Plastic Plug Sensor SLAB SENSOR INSTALLATION Screws (Used Only when Sensor Type is set to Slab) • The supplied Slab Sensor is an integral part of the SMC Slab operation. It provides the SMC with the slab temperature O Ring Sensor and detects precipitation.
(Used Only when Sensor Type is set to Outdoor) Outdoor Sensor • The SMC does not come with the Outdoor Sensor (HT# 904220- snap-in location 00). It must be ordered separately. See "Outdoor Sensor Operation Overview" on page 6.
OUTPUT WIRING WARNING • The SMC outputs do not source any power. If power is needed to a specific Each of the pump relays can output, a separate power source must be wired in series with the output. operate a maximum of ¼ HP •...
Terminals (13) through (15) • The SMC is capable of modulating a floating motorized valve. • In this case use the SMC output terminal 14 as the Common. Wire it to the 24 VAC power source (transformer). • Connect the transformer's other wire to the actuator Common terminal.
OUTPUT OUTPUT OUTPUT OUTPUT Terminals (22) and (23) • Wire the boiler or valve (V or +) terminal to the SMC terminal 22 (V+). 20 21 22 23 24 25 20 21 22 23 24 25 • Wire the boiler or valve (-) terminal to the SMC terminal 23 (-).
WIRING ALARM OUTPUT TO BMS Terminals (11) and (12) • The SMC is designed to enable the Alarm output whenever any of the sensors fail or the heating system fails. This output can be connected to a Building management System (BMS) to enable remote alarming and reporting.
3/8 ID well (HT# 904011-00) is required. Both the sensor and well must be purchased separately. See "Boiler Return Sensor" on page 11. • If the Boiler Return Sensor is connected, the SMC will display its temperature during melting and below the ISP temperature.
The System Pump and slab pump relays will remain energized for the Run-On delay period and then turn off. • Bring the two dry contact wires to the SMC 32 and 33 terminals. WIRING ThE PROVE Terminals (34) and (35) •...
WIRING TO BACNET MSTP • For the SMC to communicate over the BACnet MSTP network, the use of the BACnet Interface Module is required. The BACnet Interface Module must be ordered separately (HT# 926781-00). • Connect the provided CAT-5 cable to both the BACnet Interface Module (Product Comm Ethernet port) and the SMC's (RS485 port).
DISPLAy AND BUTTONS Display The SMC display layout provides information that gives an immediate picture of the operation status. All the information is brightly displayed. It can be viewed in virtually any light. • Each of the button functions is presented on the bottom of the display.
The SMC closes the valve to increase the boiler return temperature. "Minimum Boiler Return" on page 29. • Hold Idle at 34°F The slab temperature is below the ISP. The SMC modulates the outputs to maintain the slab at 34°F. "Idle Set Point (ISP)" on page 26. • Idle State The slab temperature is between the WWC and the ISP with no precipitation or moisture detected.
Boiler Return 142 Warm W.Cutoff 38 F MENU Idle Set Point 34 F ALERT Heating Curve To be able to change the SMC <System Settings> Hold MENU button settings the Program/Run <Maintenance> for 5 seconds Switch must be set to Program.
Hold MENU Button: <Settings>/<System Startup>/../Sensor Type outdoor ▲ ▼ • If Slab is selected, the SMC shall use the Slab sensor logic and BACK SAVE measure the slab temperature and detect precipitation. See "Slab Sensor Operation Overview" on page 4.
• The control has a coin Lithium battery (CR2032) (HT# 020002-00) that is used to maintain the control's time during power outages. This battery can maintain the clock for up to a total of 100 days. See "Activate the Battery" on page 18. SMC Installation and Operation Manual...
BACNET COMMUNICATION Available for Installers Only • The SMC control can be configured to communicate over BACnet MSTP. A BACnet Interface Module is required and must be ordered separately (HT# 926781-00). • See "BACnet Variable List" on page 37 BACNET OPTION...
▼ SELECT BACK PROGRAM SWITCh SETTING DO NOT PROGRAM To be able to change the SMC settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. SMC Installation and Operation Manual...
• The Season setting controls whether the SMC heats the slab. When set BACK SAVE to Summer, the SMC does not provide any heat to the slab. When set to Winter, the SMC shall heat the slab whenever necessary. • Set the control to Winter mode during the heating season.
• Repeat the above procedure as necessary until the lowest Curve value that still melts the snow is determined. hEATING CURVE TABLE Return Target Temperature based on the Outdoor Temperature and Heating Curve Outdoor Temperature °F SMC Installation and Operation Manual...
WWC. • The Minimum Runtime starts a timer once slab heat is activated. The SMC will continue melting until either all the moisture has evaporated off the sensor or until the Minimum Runtime has ended, whichever comes last.
(Slab Return) . This is called the Slab ΔT. • If the SMC calculates that the Slab ΔT may exceed the Max ΔT, the SMC will begin closing the slab motorized valve or decreasing the boiler modulation to help prevent excess heat from entering the slab.
BACK SAVE period when idling above the ISP or when the SMC is in CWC. It does this to help reduce the possibility of freezing the slab solution. • In addition to having a timed setting the Antifreeze option can be set to ON.
Hold MENU Button: <Settings>/<Maintenance> Boiler Runtime 840hr <Sensors Trim> <Histories> PROGRAM SWITCh SETTING <Configurations> To be able to change the SMC settings the Program/Run Switch must be ▲ ▼ BACK SELECT set to Program. The switch is located under the Enclosure Wiring Cover DO NOT for security.
• The setting adjusts the Slab Sensor's water detection sensitivity. After cleaning the sensor, set the • The Slab Sensor and the SMC are calibrated to detect moisture at the water sensitivity to zero for proper proper level, however Water Sensitivity can be temporarily adjusted to operation.
• The Season setting controls whether the SMC heats the slab. When BACK SAVE set to Summer, the SMC does not provide any heat to the slab. When set to Winter, the SMC shall heat the slab whenever necessary. • Set the control to Winter mode during the heating season.
WWC, melting begins. At this point, the WWC will serve as the set point at which the slab temperature will be held. Using the previous example, once a melting cycle has begun, the SMC will maintain the slab at 38° until the moisture is evaporated, or the minimum run time is exceeded, whichever comes last.
WWC. • The Minimum Runtime starts a timer once slab heat is activated. The SMC will continue melting until either all the moisture has evaporated off the sensor or until the Minimum Runtime has ended, whichever comes last.
• The Slab Temperature did not reach its target within 24 hours. See "Troubleshooting" on • Slab Temp. low page 39. • Supply Temp. low • The Slab Supply Temperature did not reach its target within 2 hours. SMC Installation and Operation Manual...
• Remove the wires from the sensor terminals. The display should change to 42683 read --- or open. If it does not, the SMC may be damaged. Using a multi- 31215 meter set to measure resistance, take an ohm reading across the detached 23089 sensor wires.
Page 40
• The Slab Temperature did not reach its target for a continuous 24 hours: ○ The weather is too cold for the system capability. The SMC is producing heat but may need more time due to extreme temperatures. ○ The heating system may be malfunctioning. Check the heating system components (boiler, pumps, valves).
WARRANTIES AND LIMITATIONS OF LIABILITY AND DAMAGE: Heat-Timer Corporation warrants that it will replace, or at its option, repair any Heat-Timer Corporation manufactured product or part thereof which is found to be defective in material workmanship within one year from the date of installation only if the warranty registration has been properly filled out and returned within 30 days of the date of installation.
• Control Mode = Boiler ALERT Due to the uniqueness of each installation, Heat-Timer Corp. is not responsible for any installation that is based on any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only.
SMC CONTROLLING A MODULATING WATER BOILER - WIRING SNOW MELT CONTROL ACTIVE OUTPUTS SLAB SYSTEM ALARM POWER __________________________ BURNER VALVE CLOSE Melting in Progress SLAB PUMP VALVE OPEN ALARM MENU ENCLOSED OUTPUT RATINGS: 6A RESISTIVE, 120VAC ENERGY MAXIMUM 15A TOTAL FOR ALL CIRCUITS...
• Control Mode = Motorized Valve ALERT Due to the uniqueness of each installation, Heat-Timer Corp. is not responsible for any installation that is based on any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only.
SMC MODULATING A 3-WAy MOTORIzED VALVE - WIRING using Water to Glycol heat-Exchanger and System Pump SNOW MELT CONTROL ACTIVE OUTPUTS SLAB SYSTEM ALARM POWER __________________________ BURNER VALVE CLOSE Melting in Progress Boiler Return = 142 o F SLAB PUMP...
• Control Mode = Motorized Valve ALERT Due to the uniqueness of each installation, Heat-Timer Corp. is not responsible for any installation that is based on any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only.
SMC MODULATING A 3-WAy MOTORIzED VALVE - WIRING using Water Boiler without a heat-Exchanger SNOW MELT CONTROL ACTIVE OUTPUTS SLAB SYSTEM ALARM POWER __________________________ BURNER VALVE CLOSE Melting in Progress Boiler Return = 142 o F SLAB PUMP VALVE OPEN...
• Control Mode = Motorized Valve ALERT Due to the uniqueness of each installation, Heat-Timer Corp. is not responsible for any installation that is based on any electrical or piping diagram generated. The provided illustrations are to demonstrate the control operating concept only.
SMC MODULATING A 2-WAy MOTORIzED VALVE - WIRING using Steam to Water heat-Exchanger SNOW MELT CONTROL ACTIVE OUTPUTS SLAB SYSTEM ALARM POWER __________________________ BURNER VALVE CLOSE Melting in Progress SLAB PUMP VALVE OPEN ALARM MENU OUTPUT RATINGS: 6A RESISTIVE, 120VAC...
Need help?
Do you have a question about the SMC and is the answer not in the manual?
Questions and answers