68 Cabling and connecting
Figure 4.20 – Locating a temperature probe for external battery temperature
measurements
Figure 4.21 – Locating a temperature probe for ambient temperature measurements
IM6C75AA P0914426 Standard 3.00 March 2001
4
Route the cable inside the Battery Connection Module as shown in Figure 4.17
and connect the red and black wires and the shield to the TB2 terminal block
according to the terminal assignment given in Table 4.12 and according to the
position programmed for Battery Temperature in the System Manager (1 or 2).
5
Locate and install the temperature probe used for ambient temperature
measurements as shown in Figure 4.21.
6
Run the cable attached to the probe to the Battery Connection Module and cut
the excess cable length, including the connector at the end of the cable.
7
Route the cable inside the Battery Connection Module as shown in Figure 4.17
and connect the red and black wires and the shield to the TB2 terminal block
according to the terminal assignment given in Table 4.12 and according to the
position programmed for Ambient Temperature in the System Manager (1 or 2).
8
Push back the printed circuit card and close the front cover in the top right
section of the Battery Connection Module.
9
Secure the two cables as required.
Cable to Battery
Connection Module
Probe
Top of cell
Cable to Battery
Connection Module
Mounting
Probe
surface
–end–
Insert the probe between the cell post and
the connector nut or bolt when making the
battery connection.
Use a screw or bolt of the appropriate size to locate the
probe on a surface that is most representative of the
ambient temperature.
CAUTION: The selected surface must not be affected by
hot or cold temperature from rectifiers, direct sunlight
through windows, heating or air conditioning equipment,
etc.