Emerson ASTEC Helios Candeo AP6C75AA Installation Manual page 63

Table of Contents

Advertisement

Figure 4.16 – Connector layout inside the System Manager (front cover open)
Aux power
Input ports
IN
+ - + - + - + - + - + -
1
J4
1
CANFAR
DE9 male
Ethernet port RJ45 jack
Table 4.10 – Terminal assignment of the J7 connector on the System Manager
Pin No.
Input port number
J7-1
INPUT PORT 1 +
J7-2
INPUT PORT 1 –
J7-3
INPUT PORT 2 +
J7-4
INPUT PORT 2 –
J7-5
INPUT PORT 3 +
J7-6
INPUT PORT 3 –
J7-7
INPUT PORT 4 +
J7-8
INPUT PORT 4 –
J7-9
INPUT PORT 5 +
J7-10
INPUT PORT 5 –
J7-11
INPUT PORT 6 +
J7-12
INPUT PORT 6 –
Table 4.11 – Terminal assignment of the J8 connector on the System Manager
Pin
Output port number
No.
J8-1
OUTPUT PORT 1 (NC)
J8-2
OUTPUT PORT 1 (COM)
J8-3
OUTPUT PORT 1 (NO)
J8-4
OUTPUT PORT 2 (NC)
J8-5
OUTPUT PORT 2 (COM)
J8-6
OUTPUT PORT 2 (NO)
J7
1
Alarm description
Auxiliary alarm 1
(programmable)
Auxiliary alarm 2
(programmable)
Auxiliary alarm 3
(programmable)
Generator on
(fixed)
Generator overload
(fixed)
System shutdown
(fixed)
Internal
connector
information
CH1 OUT (NO)
CH1 OUT (NC)
CH1 (COM)
CH2 OUT (NO)
CH2 OUT (NC)
CH2 (COM)
Helios Candeo Power System – AP6C75AA Installation Manual
Output ports
Alarm level
Minor (default)
Minor (default)
Minor (default)
Minor (fixed)
Major (fixed)
Major (fixed)
Pin
Output port number
No.
J8-13
OUTPUT PORT 5 (NC)
J8-14
OUTPUT PORT 5 (COM)
J8-15
OUTPUT PORT 5 (NO)
J8-16
OUTPUT PORT 6 (NC)
J8-17
OUTPUT PORT 6 (COM)
J8-18
OUTPUT PORT 6 (NO)
–continued–
Cabling and connecting 63
J8
RS-232
RS-485
DE9 male
DE9 male
Internal connector
information
CH0 IN +
CH0 IN –
CH1 IN +
CH1 IN –
CH2 IN +
CH2 IN –
CH3 IN +
CH3 IN –
CH4 IN +
CH4 IN –
CH5 IN +
CH5 IN –
Internal
connector
information
CH5 OUT (NO)
CH5 OUT (NC)
CH5 (COM)
CH6 OUT (NO)
CH6 OUT (NC)
CH6 (COM)

Advertisement

Table of Contents
loading